Planning Instructions Fire alarm system EBL512 G3, V1.1.x
33
Output no. (0-47)
Properties, like any programmable relay output.
Each input (0-15) has to be added and programmed
via WinG3
regarding:
Input no. (0-15)
Type (of input)
Properties, like any programmable input.
6.5.2
Fan control
Used for Application board type
Fan control
, e.g. "Fan control
application board" 4594, which has a front for Fan control of up to
four fans.
Fan control panel 4593 has two Fan control application boards 4594
and two Fan control fronts (see page 52).
Each Fan (0-3)
(i.e. each Fan control)
has to be added and
programmed
via WinG3.
For each fan (Fan control), also one
I/O unit for fan control 3361
(COM loop unit) has to be added and programmed via WinG3
regarding e.g:
Technical address (COM loop address 1-255)
Name (Fan control I/O unit - normally not changed)
Fan control information
I/O Matrix fan control (Fan control / fan 0-3)
Supervised
or
not supervised (Input In0)
Output latched
or
not latched
Enhanced fan control function
or
not.
Fault detection time (Input In0; 30-255 seconds)
Properties, like any programmable output.
Normally stopped
or
Normally running
6.5.3
Zone control
Used for Application board type
Zone control
.
18
Each input (0-15) has to be programmed
via WinG3 regarding:
18
Zone control is normally used on the Australian market only.