INSTALLATION AND MAINTENANCE INSTRUCTIONS

HD103B

Conventional Photoelectric Smoke& Heat Detector

SPECIFICATIONS

Operating Voltage Range:

       9 to 28VDC Volts Non-polarized

Standby Current:

               

60µA @ 24 VDC 

Maximum Alarm Current (LED on: ) 

30mA @ 24 VDC

Operating Humidity Range:        10% to 93% Relative Humidity, Non-condensing
Operating Temperature Range:

   14°F to 120°F (-10°C to 49°C)

Smoke  Sensitivity:              1.06

±

.26%FT.

Fixed Temperature Rating:          135°F (57°C)
Rate of Rise Detection:             Responds to greater than 15°F/min
Height:                        2.2˝ (55 mm) installed in Base
Diameter:

                       4.0˝ (103 mm)

Weight:                        5.5 oz. (155 g)

INSTALLATION 

BEFORE INSTALLING

NOTICE:

  This   manual   should   be   left   with   the

owner/user of this equipment.

IMPORTANT:

  The   detector   must   be   tested   and

maintained   regularly   following   NFPA  72   requirements.
The detector should be cleaned at least once a year.

GENERAL DESCRIPTION

The device is photoelectronic detector uses a state of-the-
art optical sensing chamber. This detector is designed to
provide open area protection and to be used with most
conventional fire alarm control panel. 
Two LEDs on each detector provide local 360° visible
alarm indication. They flash every 3~5 seconds indicating
that   power   is   applied   and   the   detector   is   working
properly. The LEDs latch on in alarm. LEDs will be off
when   a   trouble   condition   exists   indicating   that   the
detector sensitivity is outside the listed limit. The alarm
can be reset only by a momentary power interruption. 

INSTALLATION

NOTE

:   All   wiring   must   conform   to   applicable   local

codes, ordinances, and regulations.

NOTE

: Verify that all detector bases are installed, that

the initiating-device circuits have been tested, and that the
wiring is correct.

Remove  power  from  initiating-device   circuits   before
installing detectors.

1. Wire the sensor base per the wiring diagram, Figure 1.
2. Install the sensor into the sensor base. Push the sensor
into the base while turning it clockwise to secure it in
place.
3. After all sensors have been installed, apply power to
the control unit.

4. Test the sensor(s) as described in the TESTING
section of this manual.

5.   Notify   the   proper   authorities   that   the   system   is   in