KW1M-H Eco-POWER METER
40
◆
Working at power failure and at recovery
<At power failure>
・
It stops the demand measurement.
・
The data of present demand, demand log, monthly max. log and max.demand will be saved by the
build-in battery.
<At recovery>
・
When it recovers within the demand span, it will start measurement of present demand again with
the condition before power failure. The estimated demand and ratio of estimated demand are
calculated again at recovery and displayed.
・
When it recovers at the next demand span, it will stop the measurement until next demand span
starts.
◆
Working outline
<Present demand (PV)>
It shows demand value from the time when demand span starts to present time.
[Calculation]
CT input (calculated by Eco-POWER METER)
Present
demand (kW)
=
Integrated electric power
until present from the start
×
60 (min.
30 (min.) Demand span
=
Integrated electric power
until present from the start
×
2
Pulse input (integrated pulse input from a power meter)
Present
demand (kW)
=
(Integrated electric power
until present from the start x pulse rate)
×
60 (min.
30 (min.) Demand span
=
(Integrated electric power
until present from the start x pulse rate)
×
2
←Estimated demand (kW)
←Present demand (kW)
←Demand setting value (kW)
Alarm output