KW1M-H Eco-POWER METER
24
Clock correction setting mode
Press <ITEM/
△
><SHIFT/
▽
> to change AUTO
⇔
MANUAL
⇔
OFF.
AUTO
MANUAL
OFF
↓
<SET>
Reference frequency setting mode
*It is only when ‘MANUAL’ is selected on clock correction setting mode.
Set the reference frequency using <ITEM/
△
><SHIFT/
▽
>.
(47.5 to 63.0 Initial: 50.0)
↓
<SET>
Monitor
How to set to monitor demand using input pulse by a pulse inspector
<example>
Service pulse: 50,000pulse/kWh
CT ratio: 200 / 5 A
VT ratio: 6600 / 110 V = 60 -> (A)
[MODE1]
CT type: 5
Primary side current of CT: 200
VT ratio: A (above result)
[MODE2]
Power input type: PM
Pulse type: PULSE
Pulse constant value: 50000