KW1M-H Eco-POWER METER
72
Special
functions
Cut-off current
1.0 to 50.0%F.S (Set with setting mode)
Cut-off voltage
Below 5% of rating voltage
(Rating voltage x 0.05 x VT ratio) (Fixed)
Current threshold for
hour meter
1.0 to 100.0
%
F.S.
Accuracy
(without error
in CT and VT)
Indication accuracy
Instantaneous electric power / Integrated electric power /
Electricity charge / Conversion value
Within ± (2.0 % F.S. + 1 digit)
(at 20 °C, rated input, rated frequency, power factor 1)
In case of 5 A CT mode, within ± (2.5 % F.S. + 1 digit)
*Accuracy coverage:5 to 100% of rated current
Current
Within ± (1.0 % F.S. + 1 digit)
In case of 5 A CT mode, within ± (2.5 % F.S. + 1 digit)
(at 20 °C rated input, rated frequency, power factor 1)
*Accuracy coverage: 5 to 100 % of rated current
Voltage
Within ± (1.0 % F.S. + 1 digit)
(at 20 °C rated input, rated frequency, power factor 1)
Hour meter
±
(0.01
%
+1digit) (at 20
℃
)
Monthly accuracy:
±
260 sec.(for your reference)
In case power on start or current energizing
±
(0.01
%
+1s+1 digit) (at 20
℃
)
Temperature
characteristics
Within ± (1.0 % F.S.+ 1 digit)
In case of 5 A CT mode, within ± (1.5 % F.S. + 1 digit)
(Range of -10 to 50 °C, rated input, power factor 1)
Frequency
characteristics
Within ± (1.0 % F.S. + 1 digit)
In case of 5 A CT mode, within ± (1.5 % F.S. + 1 digit)
(Frequency change ± 5 % based on rated frequency,
rated input, power factor 1)
8.2.2 Pulse input
Input mode
Addition (Fixed)
Max. counting speed
2kHz /30Hz (Select with setting mode) *1
Pulse input
Min. input signal width:
0.25ms (When 2kHz selected) /16.7ms (When 30Hz selected)
ON:OFF ratio = 1 : 1
Input signal
Contact / No contact (open collector)
・
Impedance when shorted: Max. 1k
Ω
・
Residual voltage when shorted: Max. 2V
・
Impedance when open: Min. 100k
Ω
Output mode
HOLD (Over count)
Prescale
Decimal point
under 3-digit
Range
0.001 to 100.000 (Set with setting mode)
*1 When ‘P-THR’ is selected on Unit for pulse output setting mode, this is fixed to 50Hz.
8.2.3 Pulse for demand monitor input
Input method
Non-voltage pulse input or open-collector input
Pulse constant number
50,000(pulse/kWh) / 2,000(pulse/kWh)
Min. input signal width
0.25ms (When 2kHz selected) /16.7ms (When 30Hz selected)
Pulse rate
0.001 to 100.000 kWh/1pulse