KW1M-H Eco-POWER METER
17
Demand alarm setting mode3
DEM3
Mode defines the time to start demand monitoring.
・
It is set the range of 1 to 30 min. (Initial 10 minutes)
Ex.) When ‘10’ is set, alarm output or alarm indication ‘d’ is not occurred after 10 minutes from the
demand span started. When ‘30’ is set, it doesn’t output alarm and it doesn’t indicate alarm.
*In case of that ‘DEM1’ is set to 0.00kW, it doesn’t output alarm and it doesn’t indicate alarm.
*When ‘DEM’ is set with unit for pulse output setting mode, it outputs if all conditions DEM1, 2 and 3
are satisfied. And it indicates ‘d’ on the bottom line of the display regardless the setting of unit for
pulse output setting mode. (Refer to 5.5)
Electricity charge setting mode
RATE
Mode defines electricity charge ratio used as a standard per 1kWh.
・
It can be set the range of 0.00 to 99.99 /1kWh. (Initial 10.00)
Conversion factor setting mode
CO2
Mode defines conversion factor of carbon dioxide used as a standard per 1kWh.
・
It can be set the range of 0.000 to 9.999/1kWh. (Initial 0.410)