KW1M-H Eco-POWER METER
35
5.4.4 Format for written file
Data in SD memory card is saved with the below format as csv file.
The file format, which is saved by Eco-POWER METER, is fixed.
<File type 1 (Instantaneous value)>
(4)
(1)
(2) (3)
(1) Device information
(row 2)
KW1M
Model name
(row 3)
COM1[Unit No.01]
Station number
(based on the unit setting )
(row 4)
DT100
Target address (only the beginning)
(row 5)
MOMENT
Shows ‘instantaneous value’
(row 6)
US32 -> FLT
US16 -> FLT
S16 -> FLT
Unsigned integer 32 bit
Unsigned integer 16 bit
Signed integer 16 bit
(row 7)
kWh
Unit (based on the target address)
(2) Logging trigger
Timing to log data: 60 minutes fixed (at the end of each hour)
(3) Record number
Record number for 1 file: 24 records fixed
(4) Logging data
Logging data of the same timing: 11 data (fixed)
From column C to M
Integrated electric power, Instantaneous electric power,
R-current, S-current, T-current, R(RS)-voltage, S(RT)-voltage, T(TS)-voltage,
Power factor, Frequency, Count value
A
B
C
D
E
F
G
H
1
Date
Time
2
KW1M
KW1M
KW1M
KW1M
KW1M
KW1M
3
COM1[Unit No.0COM1[Unit No.0COM1[Un
COM1[Un
COM1[Un
COM1[Un
4
DT100
DT176
DT107
DT108
DT109
DT170 17
5
MOMENT
MOMENT
MOMENTMOMENTMOMENTMOMENT
6
US32 ->FLT
US32 ->FLT
US16 ->F US16 ->F US16 ->F US16 ->F
7
kWh
kW
A
A
A
V
8
2009/4/1 1:00:00
9
2009/4/1 2:00:00
10
2009/4/1 3:00:00
11
2009/4/1 4:00:00
12
2009/4/1 5:00:00
13
2009/4/1 6:00:00
14
2009/4/1 7:00:00
I
I
30
2009/4/1 23:00:00
31