KW1M-H Eco-POWER METER
29
MODE4 Setting flow chart
Monitor
↓
<MODE> (MODE 4 Lighting)
↓
<SET>
Auto-off setting mode
Set auto-off time by minute using <ITEM/
△
><SHIFT/
▽
>.
( 0 to 99 )
‘0’ should be set to turn always light on.
‘1~99’ should be set to turn light off at setting time (minute).
While light off, press any key to light on.
↓
<SET>
Version check mode
It displays the version of software.
↓
<SET>
Saved file type selection mode
Press <ITEM/
△
><SHIFT/
▽
> to change ON/OFF.
Initial: ON
In order to write to SD memory card with the displayed file type, set to ‘ON’.
There are 3 types and you can select ON or OFF for each type.
T1 (type1): Instantaneous value file
ON: Write data of the latest 1 month.
OFF: Not write
*Cycle is fixed to 1-hour.
ON
OFF
↓
<SET>
T2 (type2): Difference value file
ON: Write data of the latest 1 month.
OFF: Not write
*Cycle is fixed to 1-hour.
ON
OFF
↓
<SET>
T3 (type3): Instantaneous detailed value file
ON: Write the latest 5760 records (max.).
OFF: Not write
ON
OFF
↓
<SET>