KW1M-H Eco-POWER METER
20
Stand-by alarm setting mode 1
*It is only when ‘AL-S’ is selected on unit for pulse output setting mode.
Set a ratio (for the rated current) of current used for threshold value to judge stand-by power
using <ITEM/
△
><SHIFT/
▽
>.
(1.0 to 100.0)
↓
<SET>
Stand-by alarm setting mode 2
*It is only when ‘AL-S’ is selected on unit for pulse output setting mode.
Set a time used for threshold value to judge stand-by power using <ITEM/
△
><SHIFT/
▽
>.
( 0 to 9999 min.)
‘0’: Alarm is always output at the time when judging the stand-by power.
‘1 to 9999’: Alarm is output at the time when passing the setting time with
the stand-by power.
The alarm can be reset by pressing <SET>
with the instantaneous electric power display
.
After reset the alarm, start to monitor the stand-by power again.
↓
<SET>
Preset value setting mode
*It is only when ‘Cnt’ is selected on unit for pulse output setting mode.
Set preset value to output using <ITEM/
△
><SHIFT/
▽
>.
( 0 to 999999)
↓
<SET>
Demand alarm setting mode 1
Set target value for alarm using <ITEM/
△
><SHIFT/
▽
>.
( 0.00 to 9999.99)
*In case of that ‘DEM1’ is set to 0.00kW, it doesn’t output alarm and it doesn’t indicate.
↓
<SET>
Demand alarm setting mode 2
Set the hysteresis to use for decide alarm off timing using <ITEM//
△
><SHIFT/
▽
>.
( 0 to 100 )
↓
<SET>
Demand alarm setting mode 2
Set time to start demand monitor using <ITEM/
△
><SHIFT/
▽
>.
( 1 to 30 initial:10)
↓
<SET>