Commissioning and configuration
ISE SMART CONNECT KNX Panasonic
1-000C-000
© 2019 ise Individuelle Software und Elektronik GmbH
S. 37 / 69
Incompatibility at a glance
If the new firmware has a higher main version number than that of the application program, the versions
are incompatible.
Example: Incompatibility if the main version number of the firmware is higher
• Firmware version: 2.3
• Application program version: 1.3
Establishing compatibility
In case of incompatibility, you will need to uninstall the application program.
• The device remains in the existing projects.
• The device keeps the version of the application program in the ETS.
• The entire parametrisation is rejected.
• User data in the ETS is preserved.
Requirement: New product database entry exists in the catalogue.
1.
In the ETS, open the project for which the device is to be updated.
2.
Search for the new product database entry in the catalogue and add the new version of the device
to your project.
►
See Importing a new product database entry, p. 29.
3.
Select the old version of the device in the topology for your project.
4.
In the <<Topology>> window in the menu bar, select the <<Uninstall>>
→
<<Application program>>
button.
5.
Under <<Properties>>, select the <<Information>>
→
<<Application program>> tab.
6.
Select the <<Update>> button under the <<Update application program version>>.
7.
Select the newly added device and delete it again from your topology.
After uninstalling, the device behaves as in the state of delivery. The device is then
unconfigured. Then start configuration as usual.