Commissioning and configuration
ISE SMART CONNECT KNX Panasonic
1-000C-000
© 2019 ise Individuelle Software und Elektronik GmbH
S. 33 / 69
Recognising successful assignment of the physical address:
• Device: The programming LED on the device is off.
• ETS: The completed transfer is indicated on the <<History>> tab by a green marking. Programming
flag <<Adr>> is set and <<Cfg>> is not set. More information about this and other flags is available
from the ETS documentation.
8.2.4 Network settings via the device website
Requirement: The device website is open.
1.
Select <<System>>
→
<<Network settings>> in the menu bar. The network settings page will
appear.
2.
In the input field <<DNS server (optional)>>, for instance, enter the IP address of your DNS server.
3.
Click on <<Save>> below the input field. The system accepts the configuration.
8.2.5 Resetting to factory settings
When you reset the device to the factory settings, it behaves as if it were in the state of delivery.
The device is then unconfigured:
• The device remains in the existing projects.
• The device keeps the version of the application program in the ETS.
• The entire parametrisation is rejected.
• The IP settings are reset.
• The device now once again has this as the physical address: 15.15.255.
You have the following possibilities for resetting the device to the factory settings:
• Manual: Press the programming button on the device in a particular sequence.
• Automated: You select the <<Factory reset>> function on the device website.
After the IP address is assigned, you can also conveniently set the device to pro
-
gramming mode on the device website instead of pressing the programming but
-
ton on the device itself.
If you program the device from the ETS or select <<Reset device>> for the device,
the DNS server will be reset to the standard gateway. You will then need to re-con
-
figure the DNS server on the device website.
An unconfigured device is identifiable by the green APP LED flashing slowly when
the device starts up.
►