background image

 

7-11 

7.1.10  GT32 

GT32M 

Back view 

 

 

GT32T0 

 

GT32T1 

 

Installation dimensions 

 

Panel cutout dimensions 

  

Summary of Contents for GT01

Page 1: ...PROGRAMMABLE DISPLAY GT series User s Manual WUME GTH 02 2021 3 panasonic net id pidsx global Applicable Models GT01 GT11 GT21 GT02 GT02L GT05 GT12 GT32 GT03 E GT32 R GT32 E ...

Page 2: ...in these specifications Do not dismantle or remodel the product It could cause excessive exothermic heat or smoke generation Do not touch the terminal while turning on electricity It could lead to an electric shock Use the external devices to function the emergency stop and interlock circuit Connect the wires or connectors securely The loose connection could cause excessive exothermic heat or smok...

Page 3: ...2 1 Part Names 2 2 2 1 1 GT01 GT11 GT21 2 2 2 1 2 GT02 GT02L 2 4 2 1 3 GT03 E 2 6 2 1 4 GT05 GT12 GT32 GT32 R GT32 E 2 8 2 2 Terminal Layouts of COM Port 2 12 2 2 1 GT01 2 12 2 2 2 GT02 2 13 2 2 3 GT02L 2 14 2 2 4 GT11 GT12 2 15 2 2 5 GT03 E GT21 2 16 2 2 6 GT05 GT32 GT32 R GT32 E 2 17 2 3 Connecting to Screen Creation Tool GTWIN 2 18 2 3 1 TOOL Port 2 18 2 3 2 USB Port 2 18 2 3 3 Ethernet Port 2 ...

Page 4: ...ent of Battery 3 22 3 6 6 Replacement of Front Panel Protective Sheet 3 22 3 6 7 About the Waterproof Packing 3 23 Connecting with PLC 4 1 4 1 Connection with PLC 4 2 4 1 1 PLC Multiple Connection 4 2 4 1 2 GT Link Connection 4 2 4 1 3 Connecting to the PLCs made by Other Companies 4 3 4 1 4 Connecting to a Serial Device 4 3 4 1 5 Electric Supply from PLC 5 V DC type 4 3 4 2 RS232C Connection 4 4 ...

Page 5: ...ng Unusual Occurs GT02 GT02L GT03 E GT05 GT12 GT32 GT32 R GT32 E 5 5 5 3 Error Codes and How to Handle Them 5 10 5 3 1 About Error Codes 5 10 5 3 2 GT Series Error Codes 5 10 5 3 3 When Connected to a FP Series PLC 5 15 Specifications 6 1 6 1 GT01 6 2 6 1 1 General Specifications 6 2 6 1 2 Performance Specifications GT01 6 3 6 1 3 Function Specifications GT01 6 4 6 1 4 Interface Specifications GT0...

Page 6: ...Specifications GT21 6 31 6 8 3 Function Specifications GT21 6 32 6 8 4 Interface Specifications GT21 6 33 6 9 GT32 6 34 6 9 1 General Specifications GT32 6 34 6 9 2 Performance Specifications GT32 6 35 6 9 3 Function Specifications GT32 6 36 6 9 4 Interface Specifications GT32 6 37 6 9 5 Sound Output Specifications GT32T1 Only 6 38 6 10 GT32 R 6 39 6 10 1 General Specifications GT32 R 6 39 6 10 2 ...

Page 7: ...10 GT32 7 11 7 1 11 GT32 R GT32 E 7 12 7 2 Cable Specifications 7 13 7 2 1 AIGT8142 7 13 7 2 2 AIGT8152 7 13 7 2 3 AIGT8160 AIGT8162 AIGT8165 AIGT8192 7 13 7 2 4 AIGT8175 7 14 7 2 5 AIP81842 7 14 7 3 BIN HEX BCD Code Correspondence Table 7 15 7 4 ASCII Code Table 7 16 Record of changes ...

Page 8: ...n sitting upright in vertical orientation or when using a battery 20 to 55 C Ambient humidity should be 10 to 90 RH at 25 C and non condensing The upper limit of the humidity at each temperature is as below Below 40 C 90 RH 50 C 55 RH 60 C 35 RH If the product is exposed to heavy rain condensation might be caused by sudden temperature changes Usable altitude Altitude 2 000 m or less For use in pol...

Page 9: ... malfunction Operate with a single touch of the switch The touch position may shift due to aging variation If the touch position has shifted please adjust it LCD panel Do not drop or have a strong impact on the programmable display unit as glass is used for the LCD panel The liquid in the LCD panel is a hazardous substance If the LCD panel is broken do not put the leaked crystalline liquid into yo...

Page 10: ...7V8EN GT series Reference Manual GTWIN Ver 3 edition ACGM0357V13EN GT series Instruction Manual for Connection with FP WUME GTCONFP7 GT series MODBUS RTU Mode Slave Function Instruction Manual ARCT1F501E GT series General purpose Serial Communication Manual ARCT1F356E GT series Instruction Manual for Connection with Other Companies PLCs ARCT1F449E Key Point As for requesting for manuals please con...

Page 11: ...ot available Not available Keyboard 1 00 or later 2 30 or later Custom 1 00 or later 2 30 or later Other functions Recipe Recipe 1 00 or later 2 30 or later SD recipe Not available Not available Flow display 1 00 or later 2 30 or later Write device 1 00 or later 2 30 or later Sound Not available Not available Password Password 1 00 or later 2 30 or later Operation security Not available Not availa...

Page 12: ... Not available 2 A0 or later Flow display 1 00 or later 1 00 or later 2 A0 or later Write device 1 00 or later 1 00 or later 2 A0 or later Sound Not available Not available Not available Password Password 1 00 or later 1 00 or later 2 A0 or later Operation security 1 00 or later 1 00 or later 2 A0 or later Multi language exchange 1 00 or later 1 00 or later 2 A0 or later Logging function 1 00 or l...

Page 13: ... B0 or later Write device 1 00 or later 2 B0 or later Sound Not available Not available Password Password 1 00 or later 2 B0 or later Operation security 1 00 or later 2 B0 or later Multi language exchange 1 00 or later 2 B0 or later Logging function Not available Not available FP monitor function 1 20 or later 2 C0 or later Display panel sideways setting 1 00 or later 2 B0 or later Copy Cable betw...

Page 14: ...ter 2 E1 or later Flow display 1 00 or later 1 10 or later 2 E1 or later Write device 1 00 or later 1 10 or later 2 E1 or later Sound Not available Not available Not available Password Password 1 00 or later 1 10 or later 2 E1 or later Operation security 1 00 or later 1 10 or later 2 E1 or later Multi language exchange 1 00 or later 1 10 or later 2 E1 or later Logging function Not available 1 10 o...

Page 15: ...ter SD recipe 1 60 or later 2 A0 or later Flow display 1 00 or later 2 90 or later Write device 1 00 or later 2 90 or later Sound Not available Not available Password Password 1 00 or later 2 90 or later Operation security 1 10 or later 2 94 or later Multi language exchange 1 00 or later 2 90 or later Logging function 1 40 or later 2 98 or later FP monitor function 1 90 or later 2 C0 or later Disp...

Page 16: ...r later 2 60 or later SD recipe Not available Not available Flow display 1 00 or later 2 60 or later Write device 1 00 or later 2 60 or later Sound Not available Not available Password Password 1 00 or later 2 60 or later Operation security Not available Not available Multi language exchange 1 00 or later 2 60 or later Logging function Not available Not available Display panel sideways setting 1 0...

Page 17: ...0 or later Not available 2 A0 or later Flow display 1 00 or later 1 00 or later 2 97 or later Write device 1 00 or later 1 00 or later 2 97 or later Sound Not available Not available Not available Password Password 1 00 or later 1 00 or later 2 97 or later Operation security 1 00 or later 1 00 or later 2 97 or later Multi language exchange 1 00 or later 1 00 or later 2 97 or later Logging function...

Page 18: ...r later 2 70 or later SD recipe Not available Not available Flow display 1 00 or later 2 70 or later Write device 1 00 or later 2 70 or later Sound Not available Not available Password Password 1 00 or later 2 70 or later Operation security Not available Not available Multi language exchange 1 00 or later 2 70 or later Logging function Not available Not available Display panel sideways setting 1 1...

Page 19: ...r later 1 60 or later 2 A0 or later Flow display 1 00 or later 1 00 or later 2 80 or later Write device 1 00 or later 1 00 or later 2 80 or later Sound Not available 1 00 or later 2 80 or later Password Password 1 00 or later 1 00 or later 2 80 or later Operation security 1 20 or later 1 20 or later 2 94 or later Multi language exchange 1 00 or later 1 00 or later 2 80 or later Logging function 1 ...

Page 20: ... later 1 40 or later 2 F0 or later Flow display 1 40 or later 1 40 or later 2 F0 or later Write device 1 40 or later 1 40 or later 2 F0 or later Sound Not available Not available Not available Password Password 1 40 or later 1 40 or later 2 F0 or later Operation security 1 40 or later 1 40 or later 2 F0 or later Multi language exchange 1 40 or later 1 40 or later 2 F0 or later Logging function 1 4...

Page 21: ... or later 1 60 or later 2 C0 or later Flow display 1 00 or later 1 00 or later 2 C0 or later Write device 1 00 or later 1 00 or later 2 C0 or later Sound Not available Not available Not available Password Password 1 00 or later 1 00 or later 2 C0 or later 1 00 or later 1 00 or later 1 20 or later 2 C0 or later Multi language exchange 1 00 or later 1 00 or later 2 C0 or later Logging function 1 00 ...

Page 22: ...d GT Connection between multiple units with Modbus RTU master Output to Panasonic FP series X device Jump to the previous screen from Screen No Error screen Reverse display function GT01 Ver 1 37 GT11 Ver 1 27 Jump to the previous screen from Screen No Error screen Reverse display function Ver 2 983 GT05 Ver 1 42 GT12 Ver 1 12 GT32 Ver 1 52 Bug fixing Ver 2 99 GT05 Ver 1 50 GT12 Ver 1 20 GT32 Ver ...

Page 23: ...n Added the SD memory card installation flag in Basic Communication Area Added parts library Ver 2 C2 GT02 Ver 1 41 GT02L Ver 1 31 GT05 Ver 2 01 GT12 Ver 1 71 GT32 Ver 2 11 GT32 E Ver 1 11 Contrast adjustment function in GT Configuration settings GT02 GT02L GT12 Bug fixing Ver 2 D0 GT02 Ver 1 50 GT02L Ver 1 40 GT05 Ver 2 10 GT12 Ver 1 80 GT32 Ver 2 20 GT32 E Ver 1 20 Supports FP7 Supports the 64 b...

Page 24: ...55 GT03 E Ver 1 05 GT05 Ver 2 25 GT12 Ver 1 95 GT32 Ver 2 35 GT32 E Ver 1 35 Supports Windows8 Ver 2 F0 GT02 Ver 1 70 GT02L Ver 1 60 GT03 E Ver 1 10 GT05 Ver 2 30 GT12 Ver 1 A0 GT32 Ver 2 40 GT32 R Ver 1 40 GT32 E Ver 1 40 New model GT32 R Countdown timer function 180 degrees rotation display GT03 E GT32 R GT32 E Ver 2 F1 GT05 Ver 2 40 Supports TFT LCD GT05 monochrome A USB driver is automatically...

Page 25: ...Chapter 1 Features and Functions ...

Page 26: ...ble for the 3 color LED backlight type Analog touch panel provided As an analog touch panel is provided it allows maximum flexibility in the switch layout and size Screens can be created easily using a special screen creation tool Terminal GTWIN Screen contents can be easily created using the dedicated Terminal GTWIN tool Screens are put together simply by selecting parts from libraries and positi...

Page 27: ...ailable to switch the screen Switching by the instruction from PLC The screens can be switched by writing to the basic communication area from the PLC ladder program Switching with the touch screen operation The screens can be switched on the GT by using the function switching parts provided in the parts library of the GTWIN that has a function to switch the screens Switching automatically The GT ...

Page 28: ... at the same time that communication is going on between the GT and the FP series PLC This significantly boosts efficiency in the workplace For TOOL port models For USB port Ethernet port models New functions can be available by upgrading the GT The GT can be easily upgraded by downloading the latest firmware from our website or using the GT Ver_UP tool ...

Page 29: ... level of users for each part The level of operators are managed with the security password GT link function GT02 GT02L GT03 E GT05 GT12 GT32 GT32 R GT32 E This function is used to connect multiple GT units up to 32 units to a single PLC Panasonic FP series FP7 series RS485 communication is used Note Station numbers should be set to the connected GT units The both settings for GT and PLC are neces...

Page 30: ...it in CSV format This function is useful for obtaining the history of data FP monitor function GT02 GT02L GT03 E GT05 GT12 GT32 GT32 R GT32 E This function is used to monitor or change the settings and data of FP series PLC on the GT screen Without creating screens in advance or connecting to a PC the operational check of equipment in the actual environment the start up of equipment and daily main...

Page 31: ...D green red orange 5 V DC RS232C Pure black AIG02GQ02D Silver AIG02GQ03D RS422 RS485 Pure black AIG02GQ04D Silver AIG02GQ05D GT02G1 24 V DC RS232C Pure black AIG02GQ12D Silver AIG02GQ13D RS422 RS485 Pure black AIG02GQ14D Silver AIG02GQ15D GT02G2 COM port USB port USB1 1 compliant with SD memory card slot RS232C Pure black AIG02GQ22D Silver AIG02GQ23D RS422 RS485 Pure black AIG02GQ24D Silver AIG02G...

Page 32: ...5SQ02D Silver AIG05SQ03D RS422 RS485 Pure black AIG05SQ04D Silver AIG05SQ05D GT12 GT12M0 STN mono chrome LCD 320x120 dots COM port USB port USB1 1 compliant 3 color LED white red pink 24 V DC RS232C Pure black AIG12MQ02D Silver AIG12MQ03D RS422 RS485 Pure black AIG12MQ04D Silver AIG12MQ05D GT12M1 COM port USB port USB1 1 compliant with SD memory card slot RS232C Pure black AIG12MQ12D Silver AIG12M...

Page 33: ...DR Silver AIG32MQ03DR RS422 RS485 Pure black AIG32MQ04DR Silver AIG32MQ05DR GT32T R 4096 color TFT color LCD 320x240 dots RS232C Pure black AIG32TQ02DR Silver AIG32TQ03DR RS422 RS485 Pure black AIG32TQ04DR Silver AIG32TQ05DR GT32 E GT32M E TFT mono chrome LCD 320x240 dots COM port USB port USB1 1 compliant with SD memory card slot 1 color LED white 24 V DC RS232C Silver AIG32MQ03DE RS422 RS485 AIG...

Page 34: ...re black AIGT0232B Silver AIGT0232H GT11 GT11 STN monochrome LCD 240x96 dots COM port TOOL port RS232C compliant 3 color LED green red orange 24 V DC RS232C Black AIGT2030B Ashgray AIGT2030H RS422 RS485 Black AIGT2032B Ashgray AIGT2032H 1 color LED white RS232C Black AIGT2130B Ashgray AIGT2130H RS422 RS485 Black AIGT2132B Ashgray AIGT2132H GT21 GT21 256 color STN color LCD 320x240 dots COM port TO...

Page 35: ... pin loose wire cable 5 m AIGT8175 For connection to COM port of FP2 FP2SH and FP2 computer communication unit D SUB 9 pin loose wire cable 2 m AIP81842 Maintenance parts Item name Contents Product No Waterproof packing For GT01 For repair 10 in set AIGT081 For GT02 GT02L Note AIG02810 For GT03 E AIG03810E For GT05 AIG05810 For GT11 AIGT181 For GT12 AIG2810 For GT21 AIGT28121 For GT32 AIG32810 For...

Page 36: ...logo on GT GT version Ver Usable SD memory card GT02M2 GT02G2 GT03T E GT05 GT12 GT32 GT32 R GT32 E Card type Capacity SD memory card 1 39 or older 1 09 or older 1 49 or older SD memory card 32M to 1GB 1 40 or later 1 10 or later 1 50 or later SD memory card 32M to 2GB SDHC memory card CLASS2 4 4GB to 16GB 1 00 or later 1 10 or later 1 39 or older 1 09 or older 1 49 or older 1 40 or later 1 00 or l...

Page 37: ... Windows 8 Windows 7 Windows Vista Windows 2000 Windows XP 800 MB or more AIGT8001V2 Terminal GTWIN Ver 2 Upgrade model English language version AIGT8001V2R Note 1 The latest version is provided free of charge via our website https industrial panasonic com ac e dl_center software User registration is required Free of charge Note 2 The upgrade model is required for upgrading Ver 1 to Ver 2 Note 3 A...

Page 38: ... GT side connector Specification Product No D sub 9 pin Mini DIN round 5 pin L type 3 m AFC8503 Straight type 3 m AFC8503S Note A USB RS232C conversion cable is necessary to connect with a personal computer without a serial port using a PC connection cable Between PC USB and Programmable Display GT01 GT11 GT21 Recommended USB RS232C conversion cable USB conversion cable manufactured by Diatrend Co...

Page 39: ...1 15 LAN cable Ethernet port GT32T1 Either straight cable or crossing cable can be used MDI MDI X Automatic crossover function ...

Page 40: ...1 16 ...

Page 41: ...Chapter 2 Names and Functions of Parts ...

Page 42: ...2 2 2 1 Part Names 2 1 1 GT01 GT11 GT21 GT01 GT01R GT11 GT21 ...

Page 43: ...ort This port is used to connect the screen creation tool 4 Operation mode setting switches Setting the operation mode setting switches as follows when turning on the power supply enables the setting to inhibit to move to the system menu or enables to clear F ROM Setting Normal use Factory default Inhibit system menu shift Clear F ROM Switch setting Note Do not use any settings other than the abov...

Page 44: ...2 4 2 1 2 GT02 GT02L GT02M2 GT02G2 GT02M0 GT02M1 GT02G0 GT02G1 GT02L ...

Page 45: ...to install it The clock PLC device hold data alarm history and GT internal device hold data functions can be used with the backup battery 6 Operation mode setting switches Setting the operation mode setting switches as follows when turning on the power supply enables the setting to inhibit to move to the system menu or enables to clear F ROM Setting Normal use Factory default Inhibit system menu s...

Page 46: ... setting switches as follows when turning on the power supply enables the setting to inhibit to move to the system menu or enables to clear F ROM Setting Normal use Factory default Inhibit system menu shift Clear F ROM Switch setting The screen backlight flashes for a while when the F ROM clear is executed Once the F ROM clear is complete the buzzer sounds and Memory is cleared is displayed on the...

Page 47: ...over to install it The clock PLC device hold data alarm history and GT internal device hold data functions can be used with the backup battery 7 Mounting location of connector for battery 8 SD memory access lamp Except GT03M E The lamp turns on while accessing a SD memory card Do not remove the SD memory card when the lamp is lit 9 SD memory card slot Except GT03M E A SD memory card is inserted in...

Page 48: ...2 8 2 1 4 GT05 GT12 GT32 GT32 R GT32 E GT05 GT12 GT32 Standard High function ...

Page 49: ...2 9 GT32 R GT32 E ...

Page 50: ... ACT lamp GT32T1 it shows the state of communication with Ethernet Light on When linked Blinking While data reception 7 Sound output jack GT32T1 Insert the speaker with a 3 5 mini plug amplifier for using the audio output function 8 SD memory access lamp Except GT12M0 and GT12G0 The lamp turns on while accessing a SD memory card 9 Battery cover When using a backup battery to be separately purchase...

Page 51: ...ion port and power supply terminal This is a communication port RS232C or RS422 for connecting to a PLC host PC or microcomputer board and a power supply terminal for operation 13 Waterproof packing This assures that the front panel is waterproof ...

Page 52: ...e SD Send data GT External device RD Receive data GT External device RD Receive data GT External device E Terminal resistance 24 V RS232C type Pin name Name Signal direction Product No 24 V AIGT0030B AIGT0030H AIGT0130B AIGT0130H AIGT0230B AIGT0230H 0 V FG Functional ground SD Send data GT External device RD Receive data GT External device NC Not connected NC Not connected SG Signal ground Note Th...

Page 53: ...evice RD Receive data GT External device E Terminal resistance 24 V RS232C type Pin name Name Signal direction Product No 24 V AIG02MQ12D AIG02MQ13D AIG02MQ22D AIG02MQ23D AIG02GQ12D AIG02GQ13D AIG02GQ22D AIG02GQ23D 0 V FG Functional ground SD Send data GT External device RD Receive data GT External device RS Request to send GT External device CS Clear to send GT External device SG Signal ground 24...

Page 54: ... External device RS Request to send GT External device CS Clear to send GT External device SG Signal ground 5 V RS422 RS485 type Pin name Name Signal direction Product No 5 V AIG02LQ04D 0 V FG Functional ground SD Send data GT External device SD Send data GT External device RD Receive data GT External device RD Receive data GT External device E Terminal resistance ...

Page 55: ...GT External device RS Request to send GT External device CS Clear to send GT External device SG Signal ground 24 V RS422 RS485 type Pin name Name Signal direction Product No 24 V AIGT2032B AIGT2032H AIGT2132B AIGT2132H AIG12MQ04D AIG12MQ05D AIG12MQ14D AIG12MQ15D AIG12GQ04D AIG12GQ05D AIG12GQ14D AIG12GQ15D 0 V FG Functional ground SD Send data GT External device SD Send data GT External device RD R...

Page 56: ... GT External device RS Request to send GT External device CS Clear to send GT External device SG Signal ground 24 V RS422 RS485 type Pin name Name Signal direction Product No 24 V AIGT2232B AIGT2232H AIG03MQ05DE AIG03TQ15DE 0 V FG Functional ground SD Send data GT External device SD Send data GT External device RD Receive data GT External device RD Receive data GT External device E Terminal resist...

Page 57: ...e data GT External device RS Request to send GT External device CS Clear to send GT External device SG Signal ground 24 V RS422 RS485 type Pin name Name Signal direction Product No 24 V AIG05MQ04D AIG05MQ05D AIG05GQ04D AIG05GQ05D AIG05SQ04D AIG05SQ05D AIG32MQ04D AIG32MQ05D AIG32TQ04D AIG32TQ05D AIG32TQ14D AIG32TQ15D AIG32MQ04DR AIG32MQ05DR AIG32TQ04DR AIG32TQ05DR AIG32MQ05DE AIG32TQ05DE 0 V FG Fun...

Page 58: ... should not be used for any other application If using it there is a restriction on the ambient temperature The pin 5 of GT01 is N C 2 3 2 USB Port USB connection Communication with our software such as GTWIN becomes available by connecting to a PC with a USB cable Functions enabled by USB connection Through function using our PLCs Screen transfer Note If more than one programmable display unit or...

Page 59: ...able by connecting to a PC with a LAN cable Ethernet communication function Screen transfer Baud rate fixed at 115200 bps It takes at least 3 times longer than the transfer using USB Communication with our PLCs using the through function Specifying the destinations to connect enables the communication with multiple units using a HUB ...

Page 60: ...s such as IP address for the GT can be specified in the System Menu GTWIN setting Network type Ethernet Title Input an arbitrary title Up to 38 one byte characters Computer Check Acquire IP address automatically The default setting is to use the IP address currently being used in the computer Click OK to finish the setting Note When sing multiple Ethernet cards specify manually IP address When it ...

Page 61: ...to 950 seconds Default 15 it is not linked to this setting until a connection is established Connection time out Set the time out period until connection establishment within the range of 1 to 180 seconds Default 60 Setting with IP search tool Config WD exe The settings of the GT can be specified with the IP address search tool of Configurator WD Ver 1 11 or later The IP search tool Config WD exe ...

Page 62: ...2 22 ...

Page 63: ...Chapter 3 Installation and Wiring ...

Page 64: ...y other equipment that would generate high switching surges 100 mm or more The usage conditions for Tough series GT03 E GT32 E are as follows Ambient temperatures 20 to 60 C In horizontal orientation when sitting upright in vertical orientation or when using a battery 20 to 55 C Ambient humidity should be 10 to 90 RH at 25 C and non condensing The upper limit of the humidity at each temperature is...

Page 65: ...mmunity against the noise generated on the power line However it is recommended to take measures for reducing noise such as using an isolating transformer before supplying the power And it is recommended to take measures such as installing a ferrite core Allocate an independent wiring for each power supplying line PLC etc and operating device If using a power supply without a protective circuit po...

Page 66: ...ess of 1 0 to 5 0 mm should be used Use a panel that is strong enough not to be warped Clearance when the GT is installed When installing other parts to the panel or wiring cables to it provide a clearance around the panel to prevent cables from being damaged and to facilitate the installation work When performing installation work make sure to observe the following Never obstruct the slits of the...

Page 67: ...sing the fitting and screws provided with the unit Recommended screws Recommended product GT unit Size Others Quantity Mounting screw GT01 GT11 M3 20 Material SW pane head Galvanization trivalent chromate 4 pcs unit GT05 GT21 GT32 GT32 R GT32 E M3 25 GT02 GT02L GT03 E GT12 dedicated screw The GT02 GT02L GT03 E GT12 dedicated screw is not sold on the open market Using screws other than the dedicate...

Page 68: ...that the touch switches will not function properly Install the GT within the above range 3 1 7 GT21 Installation Method Secure the GT21 to the installation panel using the two fittings and four screws provided with the unit 1 Place the GT21 main unit in the installation panel 2 Insert the fittings into the grooves provided in the GT21 main unit and tighten the screws to secure the GT21 main unit t...

Page 69: ...ovided in the GT main unit and tighten the screws to secure the GT main unit to the installation panel GT05 GT32 The screw tightening torque should be 0 1 to 0 25 N m and tighten them uniformly GT32 R GT32 E The screw tightening torque should be 0 2 to 0 3 N m and tighten them uniformly Tightening the screws too hard can cause deformation of the front panel so that the touch switches will not func...

Page 70: ...T main unit in the installation panel 2 Insert the fittings into the grooves provided in the GT main unit and tighten the screws to secure the GT main unit to the installation panel Note The cross slot screwdriver No 1 must be used Tightening torque 0 2 to 0 3 N m Tightening the screws too hard can cause deformation of the front panel so that the touch switches will not function properly ...

Page 71: ...eries is horizontally long however they can be installed upright Key Point Select the vertical type when selecting a GT model in GTWIN 3 1 11 Precaution When reinstalling GT When the GT is reinstalled after being removed from the panel the water proof packing should be replaced ...

Page 72: ...inst abnormal voltage from the power supply line the power supply should be an insulated type and should be enclosed within a protective circuit If a power supply device without an internal protective circuit is being used power should always be supplied to the GT series through a fuse or a similar protective device Keep the power supply voltage within the operating voltage range Rated voltage Ope...

Page 73: ...cted to a functional earth via electronic parts the electronic parts may become damaged if there is an abnormal potential between the power line and the physical ground Do not ground the function earth when grounding a plus terminal of the power GT01 GT11 GT21 In some computers the SG terminal of RS232C port and connector shielding are connected Also the tool port shielding is connected with the f...

Page 74: ...ess When doing RS485 communication using RS422 type Please use the following cables or equivalent Appropriate electrical cables twisted cables Type Cross sectional view Conductor Insulator Cable diam Sample appropriate cable Size Resist ance at 20 C Material Thick ness Shielded twisted pair 1 25 mm2 AWG16 or greater Max 16 8 Ω km Polye thylene Max 0 5 mm Approx 8 5 mm Belden 9860 Hitachi Cable Ltd...

Page 75: ...ithout twisting the core wire The core wire should be connected without soldering it Vibration can sometimes cause soldered connections to break loose After connecting the wiring avoid subjecting the cable to stress Because of the construction of the terminal tightening the wire in the counterclockwise direction will cause a faulty connection If this happens disconnect the wire check the terminal ...

Page 76: ... Electric s E04RA190120080 or equivalent 2 Perform grounding of the cable shield Packaged with AIGT8142 RS422 RS485 type There is no RS and CS control lines Perform wiring and placement of the cable so that there is no impression of external noise on the cable and no induction Use shielded wires for distribution cables Recommended cable AIGT8152 with one ferrite core Seiwa Electric s E04RA19012008...

Page 77: ... RS and CS control lines Perform wiring and placement of the cable so that there is no impression of external noise on the cable and no induction Use shielded wires for distribution cables When using shielded cable with crossover wiring for the RS485 transmission line grounded one end E is used to set the terminating station It conforms to CE marking As conditions the following wiring is required ...

Page 78: ...s the following wiring is required 1 Install a ferrite core to the cable For GT11 only Recommended ferrite core Seiwa Electric s E04SR170730A or equivalent 2 Perform grounding of the cable shield 3 Perform grounding of the GT GT01 GT02 GT12 GT11 GT03 E GT21 GT05 GT32 GT32 R GT32 E Key Point The CE marking standards that the GT series conforms to European EMC directive 2004 108 EC European EMC stan...

Page 79: ...e end E is used to set the terminal unit It conforms to CE marking As conditions the following wiring is required 1 Fit a ferrite core to the cable For GT11 only Recommended ferrite core Seiwa Electric s E04SR170730A or equivalent 2 Perform grounding of the cable shield 3 Perform grounding of the GT GT01 GT02 GT12 GT11 GT03 E GT21 GT05 GT32 GT32 R GT32 E Key Point The CE marking standards that the...

Page 80: ...take measures for noises such as installing a ferrite core if necessary It conforms to CE marking As conditions the following wiring is required 1 Do not use a shield wire for the Ethernet cable 2 Install a ferrite core to the Ethernet cable and make one turn Recommended ferrite core Kitagawa Industries SFC 10 or equivalent GT32T1 Key Point The CE marking standards that the GT32 conforms to Europe...

Page 81: ...2M2 GT02G2 Backup battery AFPX BATT The backup battery for the FP X is used GT03T E GT05 GT12 GT32 GT32 R GT32 E Battery life Battery life when operating at a normal temperature 25 C a normal humidity 65 RH is as follows GT model life GT11 Approx 2 years GT21 GT03T E Approx 3 years GT05S GT32T0 GT32T1 GT32M R GT32T R GT32M E GT32T E GT02M2 GT02G2 Approx 5 years GT05M GT05G GT12 GT32M Backup The in...

Page 82: ...ay data Recipe data Write device FP monitor screen data Stored in the F ROM Not required Alarm history Line graph sampling Logging data of Logging function Hold GT device Hold PLC device Stored in the SRAM Required Note When using a backup battery attach the battery before the power supply is turned on ...

Page 83: ... not touch the electronic parts when removing and installing the battery 3 6 3 How to Install the Battery Backup Battery The figures below is explained using the GT32 1 Remove the battery cover 2 Connect the connector to make the red line be the side and place a battery in the circular frame 3 Fit the battery cover ...

Page 84: ...up battery turn on electricity for the time for energization and replace the battery with a new one within one minute after turning off the power supply If the battery is not replaced within the time for replacement the saved data will be lost Time for energization Time for replacement 1 min or more 10 min or more for GT32 Within 1 min 3 6 6 Replacement of Front Panel Protective Sheet About the fr...

Page 85: ...king If the panel is being detached from the GT and then reattached the waterproof packing should be replaced in order to assure that the panel remains waterproof IP65 however IP67 for GT02 GT03 E GT12 GT32 R and GT32 E Replacing the waterproof packing 1 Remove the currently attached waterproof packing Remove the attached waterproof packing from the GT 2 Attach the provided waterproof packing Take...

Page 86: ...3 24 ...

Page 87: ...Chapter 4 Connecting with PLC ...

Page 88: ...ne GT 4 1 2 GT Link Connection GT link function is a function that enables more than one GT to connect with one PLC Wiring of Power Supply It takes more than 5 seconds for all GT units to be operable after turning on the power supply of GT The time varies according to conditions and the number of connected GT units As for the power supply of GT it is recommended to use the wiring that enables mult...

Page 89: ...t is available only when it is connected with the TOOL port Restriction on the capacity of the power supply depending on the PLC model to be used The number of PLC units that can be expanded is limited PLC model Restrictions when connecting a 5 V DC type FP X The number of units which can be expanded depends on the unit type FP0 Maximum of two expansion units FP Maximum of six expansion units FP2 ...

Page 90: ...Although the terminal blocks vary according to the GT models the connection method is the same The connection diagram for 24 V DC is described with the terminal blocks other than the one for GT01 24 V DC type other than GT01 24 V DC type GT01 5 V DC type GT01 5 V DC type GT02 GT02L ...

Page 91: ...ting to the TOOL port Note Connecting to the COM port is not available Keep the cable no longer than 3 m In case of connecting to PLC with all expansion slots used prepare an external 5 V DC power supply for the GT01 due to current consumption limits When using the FP2 FP2SH check whether or not the power can be supplied from the TOOL port according to the calculation method of the number of expan...

Page 92: ...ith 24 V DC type Usable models PLC PLC communication cable Programmable display FP X FP FP0 FP0R FP e FP2 FP2SH Mini DIN 5 pin loose wire cable AIGT8162 AIGT8165 AIGT8160 24 V DC RS232C type Connecting to the TOOL port ...

Page 93: ...odels PLC PLC communication cable Programmable display FP X AFPX COM1 Loose wire cable 5 V DC 24 V DC RS232C type AFPX COM2 AFPX COM3 AFPX COM4 AFPX COM5 Connecting to the 1 channel type RS232C Connecting to the 2 channel type RS232C As for the connection to S2 and R2 for COM2 make the same connection as S1 and S2 ...

Page 94: ...4 8 Connecting to the 1 channel type RS485 and 1 channel type RS232C Connecting to the 1 channel type Ethernet and 1 channel type RS232C It cannot be connected with Ethernet ...

Page 95: ... Usable models PLC PLC communication cable Programmable display FP Loose wire cable 5 V DC 24 V DC RS232C type Connecting to the 1 channel type RS232C Connecting to the 2 channel type RS232C As for the connection to S2 and R2 for COM2 make the same connection as S1 and S2 ...

Page 96: ...4 10 Connecting to the 1 channel type RS485 and 1 channel type RS232C The connections with either one unit or two units are available ...

Page 97: ...232C Connection with FP0 FP0R COM Port Connecting to the COM port Usable models PLC PLC communication cable Programmable display FP0 FP0R RS232C type 5 V DC 24 V DC RS232C type Connecting to the COM port of FP0 FP0R ...

Page 98: ...2 6 RS232C Connection with FP e COM Port Connecting to the COM port Usable models PLC PLC communication cable Programmable display FP e Loose wire cable 5 V DC 24 V DC RS232C type Connecting to the FP e RS232C ...

Page 99: ...Communication Unit FP2 Multi Communication Unit Usable models PLC PLC communication cable Programmable display FP2 FP2CH CPU unit D SUB 9 pin loose wire cable AIP81842 5 V DC 24 V DC RS232C type FP2 Computer Communication Unit FP2 Multi Communication Unit Communication block FP2 CB232 Connecting to the TOOL port ...

Page 100: ...locks Between GT Models Although the terminal blocks vary between the 5 V DC type and 24 V DC type the connection method is the same The connection diagram is described with the terminal block for 24 V DC 24 V DC type 5 V DC type GT01 5 V DC type GT02 GT02L ...

Page 101: ...s PLC PLC communication cable Programmable display FP X AFPX COM3 Loose wire cable 5 V DC 24 V DC RS422 RS485 type Connecting to the FP X Communication cassette 1 channel type RS485 RS422 4 3 3 RS422 Connection with FP2 FP2SH COM Port Connecting to the COM port ...

Page 102: ...tion cable Programmable display FP2 Multi Communication Unit Communication block FP2 CB422 D SUB 9 pin loose wire cable AIP81842 5 V DC 24 V DC RS422 RS485 type Connecting to the FP2 Multi Communication Unit MCU Communication block RS422 ...

Page 103: ...play FP series C NET adapter AFP8536 AFP8532 AFP15401 AFP15402 5 V DC 24 V DC RS422 RS485 type Connection method Communication settings on the PLC side Specify the setting to match with the setting for the GT using the tool software at the PLC side C NET adapter setting Set the termination TERMINATE to on ...

Page 104: ...e terminal blocks vary between the 5 V DC type and 24 V DC type the connection method is the same The connection diagram is described with the terminal block for 24 V DC 24 V DC type 5 V DC type GT01 5 V DC type GT02 GT02L Note RS485 communication is performed using the RS422 terminal blocks ...

Page 105: ...Connection with FP0R COM Port Connecting to the COM port Usable models PLC PLC communication cable Programmable display FP0R RS485 type Loose wire cable 5 V DC 24 V DC RS422 RS485 type Connecting to the COM port of FP0R ...

Page 106: ...s PLC PLC communication cable Programmable display FP X AFPX COM3 Loose wire cable 5 V DC 24 V DC RS422 RS485 type AFPX COM4 AFPX COM6 Connecting to the FP X Communication cassette 1 channel type RS485 RS422 Note Check the usable GT models for 1 N communication ...

Page 107: ...4 21 Connecting to the 1 channel type RS485 and 1 channel type RS422 Note Check the usable GT models for 1 N communication ...

Page 108: ...4 22 Connecting to the 2 channel type RS485 Note Check the usable GT models for 1 N communication ...

Page 109: ...nnecting to the COM port Usable models PLC PLC communication cable Programmable display FP AFPG803 Loose wire cable 5 V DC 24 V DC RS422 RS485 type AFPG806 Connecting to the 1 channel type RS485 Note Check the usable GT models for 1 N communication ...

Page 110: ...4 24 Connecting to the 1 channel type RS485 and 1 channel type RS232C Note Check the usable GT models for 1 N communication ...

Page 111: ...85 Connection with FP e COM Port Connecting to the COM port Usable models PLC PLC communication cable Programmable display FP e RS485 type Loose wire cable 5 V DC 24 V DC RS422 RS485 type Connecting to the FP e RS485 ...

Page 112: ...cation cable Programmable display FP2 Multi Communication Unit Communication block FP2 CB485 Loose wire cable 5 V DC 24 V DC RS422 RS485 type Connecting to the FP2 Multi Communication Unit MCU Communication block RS485 Note Check the usable GT models for 1 N communication ...

Page 113: ... is sent too quickly the GT may not be able to receive it Adjust the time if necessary For our FP series FP or FP X the time can be specified using the SYS1 instruction Time taken until the GT sends a next command after receiving a response If a command is sent to quickly the connected device may not be able to receive it The time can be specified in the delay time setting for transmission in the ...

Page 114: ...tic settings mode The number of attempts is specified using the No of Retries parameter under GT Configuration Communication Parameters Handle Communication Error on GTWIN Automatically set communication conditions In the automatic settings mode if there is a response from the PLC subsequent communication is carried out under conditions matching the response The main unit configuration settings ar...

Page 115: ...tool software installed in the computer connected to the GT series as shown below is booted PLC programs can be edited through the GT series For using the through function the settings for the communication between PC and GT series and GT series and our PLC should be the same The through function does not require any special settings and is always in the standby mode For TOOL port type For USB por...

Page 116: ... the through function cannot be used Communicate at 115200 bps or lower for using the through function For the USB port type the OS installed in the connected computer must be Windows 2000 or later Restrictions on COM port connections When connecting the GT01 to the COM port of a PLC a separate external supply must be provided When using the FP programmer II An FP Programmer II cannot be connected...

Page 117: ...PLCs refer to 4 5 3 Communication Settings of PLC using FPWIN GR or 4 5 4 Communication Settings of PLC using FPWIN GR7 Make the communication settings using GTWIN 1 Select File Configuration GT Configuration from the menu bar 2 Select Communication Parameters and make the communication settings When using GTWIN Ver 3 1 Select System Setting GT Configuration GT Communication Parameters from the me...

Page 118: ...e on your computer and specify a folder for storing the driver in the Update Driver Software dialog box Driver storage folder For Windows7 64 bit Program Files x86 Panasonic ID SUNX Terminal GTWIN GTWIN_USB x64 For other Windows OS Program Files Panasonic ID SUNX Terminal GTWIN GTWIN_USB x86 For details of Update Driver Software refer to Procedure of Installing USB Driver of GTWIN Installation Gui...

Page 119: ...en using FPWIN GR 1 Select Option O Communication Settings C from the menu bar 2 Set the network type to USB GT When using FPWIN GR7 1 Select Online L Communication Settings C from the menu bar 2 Set the computer communication port to USB GT ...

Page 120: ...cting to the COM port Please match the communication format or transmission format and baud rate settings to those of the GT In addition to the transfer format and baud rate settings set the communication mode to Computer Link when using the COM port Default Comm Mode Computer Link Baud Rate 9600 bps Char Bit 8 bits Parity Odd Stop Bit 1 Note The baud rate can be changed from 9600 bps When changin...

Page 121: ... the communication settings Set the communication settings of the communication port connected to the GT to be the same as those of the GT Default Communication Mode MEWTOCOL COM Baud rate 9600 bps Data length 8 bits Parity Odd Stop bit 1 bit Note The baud rate can be changed from 9600 bps When changing it it is necessary to make the both baud rates of FP series and GT series be the same ...

Page 122: ...4 36 ...

Page 123: ...Chapter 5 Troubleshooting ...

Page 124: ...the correct keyboard number 3 GT configuration data and keyboard screen data exist in the GT but there is no base screen data 3 Transfer base screen data from GTWIN Screen displays Memory is Full The total capacity of transferred base screen data exceeds the 384 Kbyte capacity of the GT Delete part of the base screen data so that the capacity doesn t exceed the total capacity Data capacity can be ...

Page 125: ...s set on the touched area the area will not light even if touched To change the setting change the content of the backlight auto off settings Backlight goes off too quickly 1 The backlight auto off timer setting is too short 1 Change the backlight auto off timer setting Date time display is incorrect 1 The PLC s internal calendar timer used as a reference is incorrect 1 Adjust by rewriting the val...

Page 126: ...ttings noted above do not apply An incorrect screen is displayed error codes and erroneous date and time items noted above do not apply Switch doesn t work grid and validity settings noted above are correct Buzzer sounds continuously An error has occurred in the GT system 1 After confirming the safety of the device etc turn off the power supply and then turn it on again The GT CPU will be reset 2 ...

Page 127: ...vious screen Screen displays Memory is Full The total capacity of transferred base screen data exceeds the memory capacity of the GT Delete part of the base screen data so that the capacity doesn t exceed the total capacity Data capacity can be checked by going to View V Memory Usage Conditions on GTWIN menu bar When the data capacity is not over the limit invalid data could possibly be remaining ...

Page 128: ...ct when using the PLC s internal calendar timer 1 The PLC s internal calendar timer used as a reference is incorrect 1 Adjust by rewriting the value in the PLC s internal calendar timer Hold PLC Device data content isn t saved 1 No battery has been inserted 1 Purchase a battery and install it 2 The battery has run down 2 Replace the battery Date time display is incorrect 1 The PLC s internal calen...

Page 129: ...nd validity settings noted above are correct Buzzer sounds continuously An error has occurred in the GT system 1 After confirming the safety of the device etc turn off the power supply and then turn it on again The GT CPU will be reset 2 If 1 produces no change bring up the system menu and initialize the memory F ROM then transfer data again from GTWIN to the GT NOTE When doing this all base scree...

Page 130: ... Use another password Is displayed on the password change screen The password that has been already registered is tried to be registered Enter an unregistered new password Password setting incomplete Is displayed on the password change screen There are items that are not entered Enter all items Your password cannot be deleted Is displayed on the password management screen Your password was tried t...

Page 131: ... SD memory card is damaged and data cannot be read because SD memory card was ejected during save Stop the logging of data Eject the SD memory card after turning on the setting for stopping the trigger occurrence for all logging files in the record area control Activate the setting for stopping the trigger occurrence with switch parts etc Set not to save in the SD memory card Turn on the control d...

Page 132: ...are displayed when there is an error in the GT GT Unit Errors For GT01 GT11 and GT21 Code No Content Cause and solution ER00 BCC error 1 The value of BCC may be incorrect Check if there is no calculation mistake 2 There is a temporary error due to noise etc Re supply power to the PLC and GT ERFF Time up error No response from the PLC 1 The PLC connection cable is disconnected Check the connection ...

Page 133: ...ta cannot be written as the memory of the SD memory card has been exhausted Delete some data in the SD memory card or prepare a new SD memory card 1003 SD memory card reading error The data in the SD memory card cannot be read Check whether the saved data in the SD memory card is not damaged with a PC 1004 SD memory card data error The data loaded from a SD memory card does not match the GT type R...

Page 134: ...n the SRAM Transfer all data 10A0 FROM write error The firmware file loaded from a SD card is damaged Recreate the file in the SD card 1100 Ethernet IP address setting error The IP address for Ethernet is not specified correctly Check the IP address for the GT 1101 Ethernet subnet mask setting error The subnet mask for Ethernet is not specified correctly Check the subnet mask for the GT 1102 Ether...

Page 135: ... and transmission format for the GT 3 The same station number is used for more than one GT units Check the station number setting of the connected GT units 4 Another GT is reading a SD card The indication disappears when reading the SD card has completed F000 User s memory error The memory for saving screen data may be damaged Please contact us When Connected to Modbus For GT01 GT11 and GT21 Code ...

Page 136: ...hibit error A command for the address that writing is not available was sent Check the address of the sent command For GT02 GT02 GT03 E GT05 GT12 GT32 GT32 R and GT32 E Error code Error name Measures 0000 BCC error The value of BCC may be incorrect Check if there is no calculation mistake 0001 Format error A command format may be incorrect Check if it is correct 0002 NOT supported error A command ...

Page 137: ... supply power to the PLC and GT 2 There is an error in the CPU unit Re supply power to the PLC and GT ER41 Format error The PLC has been sent a command that doesn t match the protocol 1 There is a temporary error due to noise etc Re supply power to the PLC and GT 2 There is an error in the CPU unit Re supply power to the PLC and GT ER42 NOT support error The GT has sent a non supported command to ...

Page 138: ...ent a command that doesn t match the protocol 1 There is a temporary error due to noise etc Re supply power to the PLC and GT 2 There is an error in the CPU unit Re supply power to the PLC and GT ER0042 NOT support error The GT has sent a non supported command to the PLC 1 There is a temporary error due to noise etc Re supply power to the PLC and GT 2 There is an error in the CPU unit Re supply po...

Page 139: ... Made by Omron Corporation For GT01 GT11 and GT21 Code No Content Cause and solution ER00 Time up error There is no response from the PLC 1 PLC connection cable is disconnected Check the wiring of the connection cable and check for disconnection 2 It is a temporary error caused by noise etc Turn on the power supplies for PLC or GT again ER01 Cannot be executed due to operation mode The PLC receive...

Page 140: ...The GT cannot receive data PLC runaway might be the problem ER0015 Numerical data error Designated read write area is wrong Verify whether or not the reference device used with the basic communication area and each part is a readable and writable area Error codes other than these are based on Omron PLC error codes Be sure to used the PLC in monitor mode Otherwise communication will not work proper...

Page 141: ...Chapter 6 Specifications ...

Page 142: ...utoff current 10mA at default setting Insulation resistance Between power supply terminals and case 100 M or more 500 V DC measured with megohmmeter at default setting Vibration resistance 10 to 55 Hz 1 minute cycle Amplitude 0 75 mm 10 min on 3 axes Shock resistance 98 m s2 or more 4 times on 3 axes EMC Directive applicable EMC Directive EN61000 6 2 EN61000 6 4 Not applicable Noise immunity 1000 ...

Page 143: ...n orange red 1 color LED backlight white 3 color LED backlight white pink red Backlight brightness Backlight brightness can be adjusted on the menu screen or GTWIN configuration settings There are some minor variations in the backlight brightness Contrast Can be adjusted on the menu screen or GTWIN configuration settings Touch switches Touch switch Analog touch switch resistive film type Touch swi...

Page 144: ...ght lines squares circles ovals arcs elliptic arcs fan shapes elliptic fan shapes beveled squares Types of parts Switch Function switch Lamp Message Data Bar graph Clock Note2 Line graph Keyboard Custom message lamp switch Main functions Note3 Recipe Flow display Write device Multi language exchange Through function Connecting a computer to TOOL port and our PLC to COM port enables the communicati...

Page 145: ...ls For the details refer to the latest GTWIN HELP Connector Connector terminal base 8 pin Note1 2 3 Note1 The and terminals are the power supply terminals for driving the main unit Note2 Regarding power supply voltage please pay due consideration to the cable length so that the applied voltage is within the operation voltage range Note3 When supplying power from a power supply separate from the PL...

Page 146: ... 500 V DC measured with megohmmeter at default setting Vibration resistance 5 to 8 4 Hz half amplitude 3 5 mm 8 4 to 150 Hz acceleration 9 8 m s2 10 sweeps each in X Y and Z directions 1 octave min Shock resistance 147 m s2 3 times on 3 axes EC Directive applicable EN61131 2 EMC Directive Noise immunity 1000 V P P or more Pulse width 50 ns 1 s between power supply terminals based on in house measu...

Page 147: ...ytes Note2 Recipe data 64 k bytes Write device data 64 kbytes SRAM Note2 Alarm history Line graph sampling 27 5 kbytes Logging data of Logging function 64 kbytes Hold GT Device 2048 255 words Hold PLC Device 24 words Battery Note3 Backup Built in clock data Alarm history data Line graph sampling data Logging data of Logging function Internal device hold data Hold PLC Device data Life Approx 5 year...

Page 148: ...pes elliptic fan shapes beveled squares Types of parts Switch Function switch Lamp Message Data Bar graph Clock Note2 3 Line graph Alarm list Keyboard Custom message lamp switch Main functions Note4 Recipe SD recipe Note5 Flow display Write device Multi language exchange Operation security GT link PLC multiple connection Data logging Note5 FP monitor Through function Connecting a computer to USB p...

Page 149: ... from the input power supply side between 24V and 0V Note2 The and terminals are the power supply terminals for driving the main unit Interface for transferring screen data TOOL port Item Specifications Communication standard USB1 1 Connector shape Note1 USB MiniB type 5pin Male Trasmission distance Max 5 m No of connected unit with PC 1 unit Note1 Take care of handling of the connector not to add...

Page 150: ... at default setting Vibration resistance 5 to 8 4 Hz half amplitude 3 5 mm 8 4 to 150 Hz acceleration 9 8 m s2 10 sweeps each in X Y and Z directions 1 octave min Shock resistance 147 m s2 3 times on 3 axes EC Directive applicable EN61131 2 EMC Directive Noise immunity 1000 V P P or more Pulse width 50 ns 1 s between power supply terminals based on in house measurements Note2 Protective constructi...

Page 151: ...re some minor variations in the backlight brightness Contrast Contrast can be adjusted on the menu screen Touch switches Touch switch Analog touch switch resistive film type Touch switch operation 0 8 N or less Life 1 million times or more at 25 C Note1 Memory F ROM Screen data base keyboard login Flow display data FP monitor screen data 640 kbytes Recipe data 64 k bytes Write device data 64 kbyte...

Page 152: ...n No 0 to F Graphics Straight lines continuous straight lines squares circles ovals arcs elliptic arcs fan shapes elliptic fan shapes beveled squares Types of parts Switch Function switch Lamp Message Data Bar graph Clock Note2 Line graph Alarm list Keyboard Custom message lamp switch Main functions Note3 Recipe Flow display Write device Multi language exchange Operation security GT link PLC multi...

Page 153: ...ails refer to the latest GTWIN HELP Connector Connector terminal base 8 pin Note1 2 3 Note1 The and terminals are the power supply terminals for driving the main unit Note2 Regarding power supply voltage please pay due consideration to the cable length so that the applied voltage is within the operation voltage range Note3 When tightening the terminal block requires a flat blade screwdriver with a...

Page 154: ...4 Hz half amplitude 3 5 mm 8 4 to 150 Hz Acceleration 9 8 m s2 10 sweeps each in X Y and Z directions 1 octave min Shock resistance Conforms to JISB3502 and IEC61131 2 147 m s2 3 times on 3 axes EU Directive applicable EN61131 2 EMC Directive Noise immunity 1000 V P P or more Pulse width 50 ns 1 s between power supply terminals based on in house measurements Note2 Electrostatic discharge resistanc...

Page 155: ...ging function 64 kbytes Hold GT Device 2048 255 words Hold PLC Device 24 words Battery Note4 5 Backup Built in clock data Alarm history data Line graph sampling data Logging data of Logging function Internal device hold data Hold PLC Device data Life Approx 3 years at 25 C Note1 On the LCD panel bright spots points always lit or black spots points always unlit may appear or the uneven brightness f...

Page 156: ...ph Alarm list Keyboard Custom message lamp switch Switch Function switch Lamp Message Data Bar graph Clock Note2 Note3 Line graph Alarm list Alarm history Note5 Keyboard Custom message lamp switch Main functions Note4 Recipe Flow display Write device Multi language exchange Operation security GT link PLC multiple connection Recipe SD recipe Note5 Flow display Write device Multi language exchange O...

Page 157: ...eration voltage range Note3 When tightening the terminal block requires a flat blade screwdriver with a blade size of 0 4 x 2 5 or special screwdriver part No AFP0806 The tightening torque should be 0 22 to 0 3 N m Applicable wire Size Nominal cross sectional area Rated temperature AWG 28 to 16 0 08 to 1 25mm2 60 C Interface for transferring screen data USB port Item Specifications Communication s...

Page 158: ...ulation resistance Note1 Between power supply terminals and case 100 M or more 500 V DC measured with megohmmeter at default setting Vibration resistance 10 to 55 Hz 1 minute cycle Amplitude 0 75 mm 10 min on 3 axes Shock resistance 98 m s2 or more 4 times on 3 axes EC Directive applicable EN61131 2 EMC Directive Noise immunity 1000 V P P or more Pulse width 50 ns 1 s between power supply terminal...

Page 159: ...kbytes Screen data base keyboard login Flow display data FP monitor screen data 2048 kbytes Recipe data 64 k bytes Write device data 64 kbytes SRAM Note2 Alarm history Line graph sampling 27 5 kbytes Logging data of Logging function 64 kbytes Hold GT Device 2048 255 words Hold PLC Device 24 words Battery Note3 Backup Built in clock data Alarm history data Line graph sampling data Logging data of L...

Page 160: ...aight lines squares circles ovals arcs elliptic arcs fan shapes elliptic fan shapes beveled squares Types of parts Switch Function switch Lamp Message Data Bar graph Clock Note2 3 Line graph Alarm list Keyboard Custom message lamp switch Main functions Note4 Recipe SD recipe Flow display Write device Multi language exchange Operation security GT link PLC multiple connection Data logging FP monitor...

Page 161: ...t power supply side between 24V and 0V Note2 The and terminals are the power supply terminals for driving the main unit Note3 Regarding power supply voltage please pay due consideration to the cable length so that the applied voltage is within the operation voltage range Interface for transferring screen data USB port Item Specifications Communication standard USB1 1 Connector shape Note1 TYPE B T...

Page 162: ...r at default setting Vibration resistance 10 to 55 Hz 1 minute cycle Amplitude 0 75 mm 10 min on 3 axes Shock resistance 98 m s2 or more 4 times on 3 axes EC Directive applicable EMC Directive EN61000 6 2 EN61000 6 4 Noise immunity 1000 V P P or more Pulse width 50 ns 1 s between power supply terminals based on in house measurements Note3 Protective construction IP65 Initial value evaluated by us ...

Page 163: ...tive film type Touch switch operation 0 5 N or less Life 1 million times or more at 25 C Note1 Memory F ROM Screen data base keyboard Flow display data 1408 kbytes Write device data 64 kbytes SRAM Note2 Alarm history Line graph sampling 27 5 kbytes Hold GT Device 2048 255 words Hold PLC Device 24 words Battery Note3 Backup Built in clock data Alarm history data Line graph sampling data Internal de...

Page 164: ...ovals arcs elliptic arcs fan shapes elliptic fan shapes beveled squares Types of parts Switch Function switch Lamp Message Data Bar graph Clock Note2 3 Line graph Alarm list Alarm history Keyboard Custom message lamp switch Main functions Note4 Recipe Flow display Write device Multi language exchange Through function Connecting a computer to TOOL port and our PLC to COM port enables the communicat...

Page 165: ...WIN HELP Connector Connector terminal base 8 pin Note1 2 Note1 The and terminals are the power supply terminals for driving the main unit Note2 Regarding power supply voltage please pay due consideration to the cable length so that the applied voltage is within the operation voltage range Interface for transferring screen data TOOL port Item Specifications Communication standard Conforms to RS232C...

Page 166: ...inals and terminals and function earth terminal 100 M or more 500 V DC measured with megohmmeter in initial status Vibration resistance 5 to 9 Hz amplitude 3 5 mm 9 to 150 Hz acceleration 9 8 m s2 10 sweeps each in X Y and Z directions 1 octave min Shock resistance 147 m s2 3 times on 3 axes EC Directive applicable EMC Directive EN61131 2 Noise immunity 1000 V P P or more Pulse width 50 ns 1 s bet...

Page 167: ... display data FP monitor screen data 2048 kbytes Recipe data 64 k bytes Write device data 64 kbytes SRAM Note2 Alarm history Line graph sampling 27 5 kbytes Logging data of Logging function 64 kbytes Hold GT Device 2048 255 words Hold PLC Device 24 words Battery Note3 Backup Built in clock data Alarm history data Line graph sampling data Logging data of Logging function Note 4 Internal device hold...

Page 168: ...liptic arcs fan shapes elliptic fan shapes beveled squares Types of parts Switch Function switch Lamp Message Data Bar graph Clock Note2 3 Line graph Alarm list Keyboard Custom message lamp switch Main functions Note4 Recipe SD recipe Note5 Flow display Write device Multi language exchange Operation security GT link PLC multiple connection Data logging Note5 FP monitor Through function Connecting ...

Page 169: ...24V and 0V Note2 The and terminals are the power supply terminals for driving the main unit Note3 Regarding power supply voltage please pay due consideration to the cable length so that the applied voltage is within the operation voltage range Interface for transferring screen data USB port Item Specifications Communication standard USB1 1 Connector shape Note1 USB MiniB type 5pin Male Trasmission...

Page 170: ...ting Vibration resistance 10 to 55 Hz 1 minute cycle Amplitude 0 75 mm 10 min on 3 axes Shock resistance 98 m s2 or more 4 times on 3 axes EC Directive applicable EMC Directive EN61000 6 2 EN61000 6 4 Noise immunity 1000 V P P or more Pulse width 50 ns 1 s between power supply terminals based on in house measurements Note2 Protective construction IP65 Initial value evaluated by us Dustproof and dr...

Page 171: ... 1 million times or more at 25 C Note1 Memory F ROM Screen data base keyboard Flow display data 6656 kbytes Write device data 64 kbytes SRAM Note2 Alarm history Line graph sampling 27 5 kbytes Hold GT Device 2048 255 words Hold PLC Device 24 words Battery Note3 Backup Built in clock data Alarm history data Line graph sampling data Internal device hold data Hold PLC Device data Life Approx 2 years ...

Page 172: ... ovals arcs elliptic arcs fan shapes elliptic fan shapes beveled squares Types of parts Switch Function switch Lamp Message Data Bar graph Clock Note2 3 Line graph Alarm list Alarm history Keyboard Custom message lamp switch Main functions Note4 Recipe Flow display Write device Multi language exchange Through function Connecting a computer to TOOL port and our PLC to COM port enables the communica...

Page 173: ...onnector terminal base 8 pin Note1 2 Note1 The and terminals are the power supply terminals for driving the main unit Note2 Regarding power supply voltage please pay due consideration to the cable length so that the applied voltage is within the operation voltage range Interface for transferring screen data TOOL port Item Specifications Communication standard Conforms to RS232C Non insulation type...

Page 174: ...DC measured with megohmmeter at default setting Vibration resistance 10 to 55 Hz 1 minute cycle Amplitude 0 75 mm 10 min on 3 axes Shock resistance 98 m s2 4 times on 3 axes EC Directive applicable EN61131 2 EMC Directive Noise immunity 1000 V P P or more Pulse width 50 ns 1 s between power supply terminals based on in house measurements Note3 Protective construction IP65 Initial value evaluated b...

Page 175: ... 64 kbytes SRAM Note2 Alarm history Line graph sampling 27 5 kbytes Logging data of Logging function 64 kbytes Hold GT Device 2048 255 words Hold PLC Device 24 words Battery Note3 Backup Built in clock data Alarm history data Line graph sampling data Logging data of Logging function Internal device hold data Hold PLC Device data Life Approx 5 years at 25 C Approx 3 years at 25 C Note1 The touch po...

Page 176: ...s Switch Function switch Lamp Message Data Bar graph Clock Note2 3 Line graph Alarm list Keyboard Custom message lamp switch Main functions Note6 Recipe SD recipe Flow display Write device Multi language exchange Sound output Note4 Operation security GT link PLC multiple connection Data logging FP monitor Through function Connecting a computer to Ethernet port or USB port and our PLC to COM port e...

Page 177: ...purpose serial PANASONIC dedicated protocol Other companies PLC protocols For the details refer to the latest GTWIN HELP Connector Connector terminal base 8 pin Note2 3 Note1 It is internally isolated from the input power supply side between 24V and 0V Note2 The and terminals are the power supply terminals for driving the main unit Note3 Regarding power supply voltage please pay due consideration ...

Page 178: ...ote5 Simultaneous communication with the USB port is not achievable SD memory card slot Item Specifications Support media We recommend SLC SD memory cards and SLC SDHC memory cards For details on operation confirmed SD memory card and SDHC memory card visit https industrial panasonic com ac e fasys information sd card index jsp Supported format standard Conforms to SD standard Please download form...

Page 179: ...e 100 M or more 500 V DC measured with megohmmeter at default setting Vibration resistance 5 to 8 4 Hz half amplitude 3 5 mm 8 4 to 150 Hz acceleration 9 8 m s2 10 sweeps each in X Y and Z directions 1 octave min Shock resistance 147 m s2 4 times on 3 axes EC Directive applicable EN61131 2 EMC Directive Noise immunity 1000 V P P or more Pulse width 50 ns 1 s between power supply terminals based on...

Page 180: ... words Battery Note4 Backup Built in clock data Alarm history data Line graph sampling data Logging data of Logging function Internal device hold data Hold PLC Device data Life Approx 3 years at 25 C Note1 On the LCD panel bright spots points always lit or black spots points always unlit may appear or the uneven brightness flickers or crosstalk appearance of unintended shades in the area no graphi...

Page 181: ... elliptic fan shapes beveled squares Types of parts Switch Function switch Lamp Message Data Bar graph Clock Note2 3 Line graph Alarm list Keyboard Custom message lamp switch Main functions Note4 Recipe SD recipe Flow display Write device Multi language exchange Operation security GT link PLC multiple connection Data logging FP monitor Through function Connecting a computer to USB port and our PLC...

Page 182: ...de between 24V and 0V Note2 The and terminals are the power supply terminals for driving the main unit Note3 Regarding power supply voltage please pay due consideration to the cable length so that the applied voltage is within the operation voltage range Interface for transferring screen data USB port Item Specifications Communication standard USB1 1 Connector shape Note1 TYPE B Trasmission distan...

Page 183: ...4 Hz half amplitude 3 5 mm 8 4 to 150 Hz acceleration 9 8 m s2 10 sweeps each in X Y and Z directions 1 octave min Shock resistance 147 m s2 4 times on 3 axes EC Directive applicable EN61131 2 EMC Directive Noise immunity 1000 V P P or more Pulse width 50 ns 1 s between power supply terminals based on in house measurements Note3 Electrostatic discharge resistance 6kV Contact Discharge EN61000 4 2 ...

Page 184: ... words Battery Note4 Backup Built in clock data Alarm history data Line graph sampling data Logging data of Logging function Internal device hold data Hold PLC Device data Life Approx 3 years at 25 C Note1 On the LCD panel bright spots points always lit or black spots points always unlit may appear or the uneven brightness flickers or crosstalk appearance of unintended shades in the area no graphi...

Page 185: ... Lamp Message Data Bar graph Clock Note2 3 Line graph Alarm list Keyboard Custom message lamp switch Main functions Note4 Recipe SD recipe Flow display Write device Multi language exchange Operation security GT link PLC multiple connection Data logging FP monitor Through function Connecting a computer to USB port and our PLC to COM port enables the communication between the PLC and the computer Co...

Page 186: ...te2 The and terminals are the power supply terminals for driving the main unit Note3 Regarding power supply voltage please pay due consideration to the cable length so that the applied voltage is within the operation voltage range Interface for transferring screen data USB port Item Specifications Communication standard USB1 1 Connector shape Note1 TYPE B Trasmission distance Max 5 m No of connect...

Page 187: ...Chapter 7 Dimensions and Other Documentation ...

Page 188: ...7 2 7 1 Dimensions 7 1 1 GT01 GT01R Installation dimensions Panel cutout dimensions ...

Page 189: ...7 3 7 1 2 GT02 Installation dimensions Panel cutout dimensions ...

Page 190: ...7 4 7 1 3 GT02L Installation dimensions Panel cutout dimensions ...

Page 191: ...7 5 7 1 4 GT03M E Installation dimensions Panel cutout dimensions ...

Page 192: ...7 6 7 1 5 GT03T E Installation dimensions 60 connector Panel cutout dimensions 87 5 1 0 76 5 1 0 Unit mm Applicable panel thickness 1 0 to 5 0 mm ...

Page 193: ...7 7 7 1 6 GT05 Installation dimensions Panel cutout dimensions ...

Page 194: ...7 8 7 1 7 GT11 Installation dimensions Panel cutout dimensions ...

Page 195: ...7 9 7 1 8 GT12 Installation dimensions Panel cutout dimensions ...

Page 196: ...7 10 7 1 9 GT21 Installation dimensions Panel cutout dimensions ...

Page 197: ...7 11 7 1 10 GT32 GT32M Back view GT32T0 GT32T1 Installation dimensions Panel cutout dimensions ...

Page 198: ...7 12 7 1 11 GT32 R GT32 E Installation dimensions Panel cutout dimensions ...

Page 199: ...7 13 7 2 Cable Specifications 7 2 1 AIGT8142 7 2 2 AIGT8152 7 2 3 AIGT8160 AIGT8162 AIGT8165 AIGT8192 ...

Page 200: ...7 14 7 2 4 AIGT8175 7 2 5 AIP81842 ...

Page 201: ...00 0001 0001 0001 0001 0001 0001 1000 1001 0000 0001 0010 0011 0100 0101 16 17 18 19 20 21 22 23 0010 0011 0012 0013 0014 0015 0016 0017 00000000 00000000 00000000 00000000 00000000 00000000 00000000 00000000 00010000 00010001 00010010 00010011 00010100 00010101 00010110 00010111 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0001 0001 0001 0001 0010 0010 0010 0010...

Page 202: ...7 16 7 4 ASCII Code Table ...

Page 203: ...ed vertical type display function GT05 GT32 GT32 E Added device change function Sixth edition Added new models GT03 E Monochrome and Color types Seventh edition Eighth edition Added new model GT32 R Ninth edition Added the description of through function Error correction Tenth edition 3 1 3 Installation Space Added precautions 5 3 1 About Error Codes Added error codes Added precautions on PLC erro...

Page 204: ...require the high level of reliability and safety Acceptance inspection In connection with the Products you have purchased from us or with the Products delivered to your premises please perform an acceptance inspection with all due speed and in connection with the handling of our Products both before and during the acceptance inspection please give full consideration to the control and preservation...

Page 205: ......

Page 206: ...t Panasonic Industrial Devices SUNX Co Ltd 2021 WUME GTH 02 March 2021 Panasonic Industrial Devices SUNX Co Ltd https panasonic net id pidsx global Please visit our website for inquiries and about our sales network ...

Reviews: