M A I N T E N A N C E
122 / 222
XS700-XS3000_manual_ger_eng_it_V1.1.2.doc
...........................................................
R. Kistler
7.3 When to replace batteries
If the
display lights up, the alarm signal sounds and the "Battery
maintenance necessary" message lights up, the batteries must
be replaced. Please contact your dealer or ONLINE to order new
batteries.
7.4 Replacing batteries
NOTE
Do not remove the batteries while the UPS system is running
in battery mode.
The hot-swap function, allows the batteries to be replaced without
shutting down the UPS system and without having to disconnect the
connected loads.
If you would prefer to disconnect the UPS system from the mains
before replacing the batteries, please read the "
Shutting down the
UPS system"
section.
CAUTION
Maintenance work should be performed by a qualified tech-
nician who is experienced in working with batteries and un-
derstands the necessary safety precautions. Keep unauthor-
ised personnel away from batteries
Batteries can pose a risk of electric shock or injury due to
high short-circuit currents. Comply with the following safety
precautions:
o
Remove watches, jewellery and other metal objects from
your body
o
Use only tools with insulated grips and handles
o
Do not place tools or metal parts on to the batteries
The batteries may only be replaced with the same number of
batteries of the same type
Summary of Contents for ONLINE XANTO S 1000
Page 2: ...2 222 XS700 XS3000_manual_ger_eng_it_V1 1 2 doc R Kistler ...
Page 74: ...74 222 XS700 XS3000_manual_ger_eng_it_V1 1 2 doc R Kistler ...
Page 76: ...76 222 XS700 XS3000_manual_ger_eng_it_V1 1 2 doc R Kistler ...
Page 148: ...148 222 XS700 XS3000_manual_ger_eng_it_V1 1 2 doc R Kistler ...
Page 150: ...150 222 XS700 XS3000_manual_ger_eng_it_V1 1 2 doc R Kistler ...
Page 222: ...222 222 XS700 XS3000_manual_ger_eng_it_V1 1 2 doc R Kistler ...