O P E R A T I O N
96 / 222
XS700-XS3000_manual_ger_eng_it_V1.1.2.doc
...........................................................
R. Kistler
4. Operation
This section contains information about the use of the XANTO
S 700 - 3000VA, such as the use of the control panel on the front
side, operating modes, starting and shutting down the UPS system,
switching between different operating modes, calling up the event
log, setting the power strategy and configuring the bypass settings,
load segments, battery settings and communication.
4.1 Functions on the control panel
Figure 9: XANTO S control panel (model XANTO S 3000R
)
Display Status Description
Green
ON
The UPS system is running in normal mode.
Flashes A new information message is active.
Yellow
ON
The UPS system is in battery mode.
Flashes The battery voltage lies below the warning message threshold.
Yellow
ON
The UPS system is in bypass mode.
The UPS system functions during the HE mode properly in
the bypass mode.
Red
ON
A warning message is active or there is a fault present
(see
Troubleshooting
).
Table 2: Display descriptions