I N S T A L L A T I O N
95 / 222
XS700-XS3000_manual_ger_eng_it_V1.1.2.doc
...........................................................
R. Kistler
8. Press the
esc
button on till the display shows the power on
mode.
The UPS system should be in the "Normal mode".
9. If additional battery modules are installed, the number of in-
stalled battery modules must be set in the UPS system (see
Operation
– Configuring the UPS system for battery modules
).
10. To change the factory settings, please read the
User Settings
section in the
Operation
chapter.
NOTE
ONLINE recommend setting the date and time
When starting for the first time, the output frequency is set to
the value of the input frequency (the automatic detection is
enabled by default).
When starting for the first time, the output voltage is set to
230 V (the automatic detection is disabled by default).
11. If an additional emergency-off switch was installed, the emer-
gency-off function must also be checked:
To check this, operate the emergency-off switch and check
that the status switches on the display of the UPS system.
Deactivate the emergency-off switch and restart the UPS
system.
NOTE
The internal batteries will charge up to 90% of their capacity
in less than three hours. ONLINE recommends charging the
batteries for 48 hours after installation or after a longer peri-
od of storage. If additional battery modules were installed,
please refer to the charging times in the
Technical Data
sec-
tion.
Summary of Contents for ONLINE XANTO S 1000
Page 2: ...2 222 XS700 XS3000_manual_ger_eng_it_V1 1 2 doc R Kistler ...
Page 74: ...74 222 XS700 XS3000_manual_ger_eng_it_V1 1 2 doc R Kistler ...
Page 76: ...76 222 XS700 XS3000_manual_ger_eng_it_V1 1 2 doc R Kistler ...
Page 148: ...148 222 XS700 XS3000_manual_ger_eng_it_V1 1 2 doc R Kistler ...
Page 150: ...150 222 XS700 XS3000_manual_ger_eng_it_V1 1 2 doc R Kistler ...
Page 222: ...222 222 XS700 XS3000_manual_ger_eng_it_V1 1 2 doc R Kistler ...