7
.
EtherNet/IP Connection Procedure
61
7.5.2. Checking Sent and Received Data
Check that correct data is sent and received.
In this procedure, the output of the netTAP is performed, which may have a risk
of unexpected operation of the devices connected to the netTAP.
Ensure safety before you proceed with this operation check described here.
If you cannot ensure safety, do not proceed. When you perform this operation
check, make sure to complete all the steps and make the output of the netTAP
safe.
If you wire the I/O in a state where the devices are powered ON, this may cause
damage to the devices.
Always read and follow the information provided in all safety precautions in the
manuals for each device to be wired.
If you change the variable values on a Watch Tab Page when Sysmac Studio is
online with the CPU Unit, the devices connected to the Controller may operate
regardless of the operating mode of the CPU Unit.
Always ensure safety before you change the variable values on a Watch Tab
Page when Sysmac Studio is online with the CPU Unit.
1
Select
Watch Tab Page
from the
View Menu in Sysmac Studio.
2
The Watch (Project)1 Tab Page is
displayed.
3
Click
Input Name
in the
Name
Column.
Enter the following variables and
select
Binary
as the display
format.
EIP002_data_OUT
:
Binary
EIP002_data_IN
:
Binary