77
Press the CLR Key or the SHIFT and TR Keys to return to the normal moni-
toring display.
If an erroneous input has been made, press the CLR Key to restore the sta-
tus prior to the input. Then enter the correct input.
4-3-23 Force Set, Reset
This operation is used to force bits ON (force set) or OFF (force reset) and is
useful when debugging the program or checking output wiring. It is possible
in MONITOR or PROGRAM mode only.
RUN
MONITOR
PROGRAM
No
OK
OK
Caution
Check that there is no effect on equipment before using force set/reset.
1, 2, 3...
1. Monitor the status of the desired bit according to the procedure described in
4-3-11 Bit, Digit, Word Monitor. If two or more words are being monitored,
the desired bit should be leftmost on the display.
(Multiple address monitor)
00000 20000
^OFF ^ON
2. Press the SET Key to force the bit ON or press the RESET Key to force the
bit OFF.
SET
00000 20000
ON ^OFF
The cursor in the lower left corner of the display indicates that the force set/
reset is in progress. Bit status will remain ON or OFF only as long as the key
is held down; the original status will return one cycle after the key is
released.
3. Press the SHIFT+SET or SHIFT+RESET Keys to maintain the status of the
bit after the key is released. In this case, the force-set status is indicated by
an “S” and the force-reset status is indicated by an “R.”
To return the bit to its original status, press the NOT Key or perform the Clear
Force Set/Reset operation. Refer to 4-3-24 Clear Force Set/Reset for
details.
Forced status will also be cleared when the PC’s operating mode is changed
(unless SR 25211 is ON, in which case forced status will not be cleared
when changing from PROGRAM to MONITOR mode) or when operation
stops as the result of a fatal error or power interruption.
4-3-24 Clear Force Set/Reset
This operation is used to restore the status of all bits which have been force
set or reset. It is possible in MONITOR or PROGRAM mode only.
RUN
MONITOR
PROGRAM
No
OK
OK
Caution
Check that there is no effect on equipment before using clear force set/reset.
1, 2, 3...
1. Press the CLR Key to bring up the initial display.
2. Press the SET and then the RESET Key. A confirmation message will
appear.
SET
RESET
00000FORCE RELE?
Programming Console Operations
Section 4-3
Summary of Contents for SYSMAC CPM1
Page 1: ...Cat No W262 E1 4 Programmable Controllers SYSMAC CPM1 OPERATION MANUAL ...
Page 2: ...CPM1 Programmable Controllers Operation Manual Revised February 1998 ...
Page 116: ...105 Appendix B Dimensions All dimensions are in millimeters CPM1 10CDR j 121 130 85 81 90 ...
Page 118: ...Appendix B Dimensions 107 CPM1 20EDR 81 90 171 180 85 ...
Page 119: ...Appendix B Dimensions 108 CPM1 CIF01 90 81 21 30 205 50 56 CPM1 CIF11 90 81 21 30 205 50 61 ...