46
3-4-9 NT Link Connections
High-speed communications can be achieved by providing a direct access
through the use of the NT Link between the CPM1 and Programmable Terminal.
Programmable Terminal
RS-232C Cable
CPM1
CPU Unit
RS-232C
Adapter
Note The NT Link can only be used when the RS-232C Adapter (CPM1-CIF01) is con-
nected.
Set the DIP switch of the RS-232C Adapter (CPM1-CIF01) to the NT (bottom)
side.
The following diagram shows the wiring in the RS-232C cable used to connect a
CPM1 to a Programmable Terminal.
1
2
3
4
5
6
–
SD
RD
RS
CS
–
–
–
SG
7
8
9
FG
2
3
4
5
6
7
8
9
SD
RD
RS
CS
–
–
SG
9
RS-232C Adapter
Pin No.
Signal
–
Pin No.
Signal
PT
1/Cover
Wiring and Connections
Section 3-4
Summary of Contents for SYSMAC CPM1
Page 1: ...Cat No W262 E1 4 Programmable Controllers SYSMAC CPM1 OPERATION MANUAL ...
Page 2: ...CPM1 Programmable Controllers Operation Manual Revised February 1998 ...
Page 116: ...105 Appendix B Dimensions All dimensions are in millimeters CPM1 10CDR j 121 130 85 81 90 ...
Page 118: ...Appendix B Dimensions 107 CPM1 20EDR 81 90 171 180 85 ...
Page 119: ...Appendix B Dimensions 108 CPM1 CIF01 90 81 21 30 205 50 56 CPM1 CIF11 90 81 21 30 205 50 61 ...