100
Memory Error Check
Memory error occurred.
AR 1309 ON?
AR 1314 ON?
AR 1308 ON?
Replace the CPU
Unit.
Check/correct data backed up by
capacitor and clear error.
Check the program, correct any
errors, and clear the error.
End
No
Yes
No
No
Yes
No
Yes
AR 1310 to
AR 1312 ON?
Check the error indicated by
the flag that is ON, correct set-
tings as required, and write
data to the flash memory.
No
Turned ON during
startup?
Yes
Yes
Check the external
environment.
No
Troubleshooting Flowcharts
Section 5-6
Summary of Contents for SYSMAC CPM1
Page 1: ...Cat No W262 E1 4 Programmable Controllers SYSMAC CPM1 OPERATION MANUAL ...
Page 2: ...CPM1 Programmable Controllers Operation Manual Revised February 1998 ...
Page 116: ...105 Appendix B Dimensions All dimensions are in millimeters CPM1 10CDR j 121 130 85 81 90 ...
Page 118: ...Appendix B Dimensions 107 CPM1 20EDR 81 90 171 180 85 ...