3
High-speed Counter
CPM1 PCs have a high-speed counter that can be used in incremental mode or
up/down mode. The high-speed counter can be combined with input interrupts
to perform target value control or zone comparison control that isn’t affected by
the PC’s cycle time.
Analog Setting Function
The CPM1 PCs have 2 analog volume controls that can be used to make manual
analog settings.
Host Link Communications
The CPM1 PCs are compatible with the Host Link, which allows communica-
tions with personal computers. The CPM1 using the Host Link can also commu-
nicate with Programmable Terminal using host link commands.
An RS-232C Adapter is used for 1-to-1 communications and an RS-422 Adapter
is used for 1-to-n communications.
1-to-1 Link
A data link can be created with a data area in another CPM1, CQM1, or C200HS
PC. An RS-232C Adapter is used to make the 1-to-1 connection.
NT Link Communications
High-speed operations can be achieved by providing a direct access by con-
necting the CPM1 to the Programmable Terminal through the NT Link Interface.
An RS-232 Adapter is used for this connection.
Standard Peripheral Devices The CPM1 uses the same Programming Consoles, SYSMAC Support Software
(SSS), and Ladder Support Software (LSS) as the Mini H-type and CQM1 PCs.
Programming operation is possible through the PT screen by using an OMRON
PT that has a built-in Programming Console function.
1-1-2 I/O Terminal – IR Bit Allocation
The following table shows which IR bits are allocated to the I/O terminals on the
CPM1’s CPU Unit and Expansion I/O Unit.
Note The Expansion I/O Units consist of models with relay output. The Expansion I/O
Units can also be connected to CPM1A Expansion I/O Units (sink type or source
type) with transistor output. For more information about the transistor-output
Expansion I/O Units of the CPM1A, refer to the CPM1A Operation Manual
(W317).
Number of
I/O Terminals
CPU Unit Terminals
Expansion I/O Unit Terminals
Power
Supply
Model Number
I/O Terminals
on the CPU
Unit
Inputs
Outputs
Inputs
Outputs
Supply
10
6 points:
4 points:
12 points:
8 points:
AC
CPM1-10CDR-A
00000 to 00005
01000 to 01003
00100 to 00111
01100 to 01107
DC
CPM1-10CDR-D
20
12 points:
8 points:
12 points:
8 points:
AC
CPM1-20CDR-A
00000 to 00011
01000 to 01007
00100 to 00111
01100 to 01107
DC
CPM1-20CDR-D
30
18 points:
12 points:
12 points:
8 points:
AC
CPM1-30CDR-A
00000 to 00011
01000 to 01007
00200 to 00211
01200 to 01207
DC
CPM1-30CDR-D
00100 to 00105
01100 to 01103
36 points:
00200 to 00211
24 points:
01200 to 01207
AC
CPM1-30CDR-A-V1
(Available soon)
00300 to 00311
00400 to 00411
01300 to 01307
01400 to 01407
DC
CPM1-30CDR-D-V1
(Available soon)
Programming is Possible
Using the PT
CPM1 Features and Functions
Section 1-1
Summary of Contents for SYSMAC CPM1
Page 1: ...Cat No W262 E1 4 Programmable Controllers SYSMAC CPM1 OPERATION MANUAL ...
Page 2: ...CPM1 Programmable Controllers Operation Manual Revised February 1998 ...
Page 116: ...105 Appendix B Dimensions All dimensions are in millimeters CPM1 10CDR j 121 130 85 81 90 ...
Page 118: ...Appendix B Dimensions 107 CPM1 20EDR 81 90 171 180 85 ...
Page 119: ...Appendix B Dimensions 108 CPM1 CIF01 90 81 21 30 205 50 56 CPM1 CIF11 90 81 21 30 205 50 61 ...