2-2-3 Communications Adapter Components
RS-232C Adapter
1. Mode Setting Switch
2. Connector
3. RS-232C port
RS-232C Port Pin allocation
1
2
3
4
5
6
7
8
9
FG
SD
RD
RTS
CTS
DCD
DSR
DTR
SG
1, 2, 3...
1. Mode Setting Switch
Set this switch to “HOST” when using a Host Link system to connect to a
personal computer. Set this switch to “NT” when connecting to a Program-
mable Terminal or PC for 1:1 link.
2. Connector
Connects to the CPU Unit’s Peripheral Port.
3. RS-232C Port
Connects to the RS-232C cable from the other device such as a personal
computer, Peripheral Device, or Programmable Terminal.
RS-422 Adapter
1. Termination Resistance Switch
2. Connector
3. RS-422 port
RS-422 Port Pin allocation
FG
SG
SDB
SDA
RDB
RDA
1, 2, 3...
1. Termination Resistance Switch
Set the termination resistance switch to “ON” (upper side) for the Link
Adapters on both ends of the Host Link system and for the RS-422 Adapter.
2. Connector
Connects to the CPU Unit’s Peripheral Port.
3. RS-422 Port
Connects to the Host Link network.
Note The CPM1-CIF01/CIF11 are used with the CPM1A, CPM1, and SRM1 only. Do
not use them with a C200HS PC or other PC.
Unit Components
Section 2-2
Summary of Contents for SYSMAC CPM1
Page 1: ...Cat No W262 E1 4 Programmable Controllers SYSMAC CPM1 OPERATION MANUAL ...
Page 2: ...CPM1 Programmable Controllers Operation Manual Revised February 1998 ...
Page 116: ...105 Appendix B Dimensions All dimensions are in millimeters CPM1 10CDR j 121 130 85 81 90 ...
Page 118: ...Appendix B Dimensions 107 CPM1 20EDR 81 90 171 180 85 ...
Page 119: ...Appendix B Dimensions 108 CPM1 CIF01 90 81 21 30 205 50 56 CPM1 CIF11 90 81 21 30 205 50 61 ...