29
Automatic Restart
When the supply voltage recovers to a value higher than 85% of the rated value,
operations resumes automatically.
Duration of power interrupt
(Below 85% of rated voltage)
10 ms (2 ms)
Under
Over
Normal operation
Operation may stop.
All outputs go OFF when
operations stop.
Note The CPM1 may repeat stop/start operations if the supply voltage of less than
85% of the rated value gradually goes up or down.
If this affects the equipment, etc., provide a protection circuit which shuts off the
output if the supply voltage is not above the rated value.
Time Up to the Start of Operation
The time from when the power supply is turned on to when the operation starts
varies depending on the operation conditions such as power supply voltage,
configuration, ambient temperature, etc. The minimum time is approximately
300 ms.
3-2
Selecting an Installation Site
The CPM1 is resistant to harsh conditions and highly reliable, but installing the
PC in a favorable site will maximize its reliability and operating lifetime.
Caution
Be sure to install the CPM1 correctly, as outlined in this manual. Failure to do so
may result in Unit malfunction.
3-2-1 Installation Site Conditions
Note Do not install the CPM1 under any of the following conditions.
•
Locations subject to direct sunlight.
•
Locations subject to a temperature below 0
°
C or over 55
°
C.
•
Locations subject to a humidity below 10% or over 90%.
•
Locations subject to condensation as the result of severe changes in tempera-
ture.
•
Locations subject to corrosive or flammable gases.
•
Locations subject to dust (especially iron dust) or salts.
•
Locations subject to shock or vibration.
•
Locations subject to exposure to water, oil, or chemicals.
Be sure that the conditions at the installation site conform to the CPM1’s general
specifications. Refer to 2-1-1 General Specifications for details.
Note Provide proper shielding when installing in the following locations:
•
Locations subject to static electricity or other sources of noise.
•
Locations subject to strong electromagnetic fields.
•
Locations subject to possible exposure to radiation.
•
Locations near to power supply lines.
Selecting an Installation Site
Section 3-2
Summary of Contents for SYSMAC CPM1
Page 1: ...Cat No W262 E1 4 Programmable Controllers SYSMAC CPM1 OPERATION MANUAL ...
Page 2: ...CPM1 Programmable Controllers Operation Manual Revised February 1998 ...
Page 116: ...105 Appendix B Dimensions All dimensions are in millimeters CPM1 10CDR j 121 130 85 81 90 ...
Page 118: ...Appendix B Dimensions 107 CPM1 20EDR 81 90 171 180 85 ...
Page 119: ...Appendix B Dimensions 108 CPM1 CIF01 90 81 21 30 205 50 56 CPM1 CIF11 90 81 21 30 205 50 61 ...