72
4-3-15 Signed Decimal Monitor
This operation converts the contents of the specified word from signed hexa-
decimal (two’s complement format) to signed decimal for display. The opera-
tion can be executed while using I/O monitoring, multiple address monitoring
or 3-word monitoring.
RUN
MONITOR
PROGRAM
OK
OK
OK
1, 2, 3...
1. Monitor the word that is to be used for decimal monitor with sign. During mul-
tiple address monitoring, the leftmost word will be converted.
(Multiple address monitor)
c000 cL00 20000
FFF0 0000 ^OFF
2. Press the SHIFT+TR Keys to display the leftmost word as signed decimal.
SHIFT
TR
c000
Ć00016
At this point, the contents of the displayed word can be changed with a
signed-decimal input. Refer to 4-3-21 Signed Decimal Data Modification.
3. Press the CLR Key or the SHIFT+TR Keys to end the unsigned decimal dis-
play and return to normal monitoring.
CLR
c000 cL00 20000
FFF0 0000 ^OFF
4-3-16 Unsigned Decimal Monitor
This operation is used to convert hexadecimal data in a word to unsigned
decimal for display. The operation can be executed while using I/O monitor-
ing, multiple address monitoring or 3-word monitoring.
RUN
MONITOR
PROGRAM
OK
OK
OK
1, 2, 3...
1. Monitor the word that is to be used for decimal monitor without sign. During
multiple address monitoring, the leftmost word will be converted.
Multiple address monitoring
c000 cL00 20000
FFF0 0000 ^OFF
2. Press the SHIFT+TR+NOT Keys to display the leftmost word as unsigned
decimal.
SHIFT
TR
NOT
c000
65520
At this point, the contents of the displayed word can be changed with an
unsigned-decimal input. Refer to 4-3-22 Unsigned Decimal Data Modifica-
tion.
3. Press the CLR Key or the SHIFT+TR Keys to end the unsigned decimal dis-
play and return to normal monitoring.
CLR
c000 cL00 20000
FFF0 0000 ^OFF
Programming Console Operations
Section 4-3
Summary of Contents for SYSMAC CPM1
Page 1: ...Cat No W262 E1 4 Programmable Controllers SYSMAC CPM1 OPERATION MANUAL ...
Page 2: ...CPM1 Programmable Controllers Operation Manual Revised February 1998 ...
Page 116: ...105 Appendix B Dimensions All dimensions are in millimeters CPM1 10CDR j 121 130 85 81 90 ...
Page 118: ...Appendix B Dimensions 107 CPM1 20EDR 81 90 171 180 85 ...
Page 119: ...Appendix B Dimensions 108 CPM1 CIF01 90 81 21 30 205 50 56 CPM1 CIF11 90 81 21 30 205 50 61 ...