3-2-2 Panel/Cabinet Installation
Consider PC operation, maintenance, and surrounding conditions when instal-
ling the CPM1 in a panel or cabinet.
Overheating
The operating temperature range for the CPM1 is 0
_
C to 55
_
C. Be sure that
there is adequate ventilation for cooling.
•
Allow enough space for air circulation.
•
Do not install the CPM1 above equipment that generates a large amount of
heat, such as heaters, transformers, or large resistors.
•
Install a cooling fan or system when the ambient temperature exceeds 55
_
C.
Control panel
Fan
Air vent
CPM1
Electrical Noise
Power lines and high-voltage equipment can cause electrical noise in the PC.
•
Do not install the CPM1 in a panel or cabinet with high-voltage equipment.
•
Allow at least 200 mm between the CPM1 and nearby power lines.
CPM1
200 mm min.
200 mm min.
Accessibility
Ensure that the CPM1 can be accessed for normal operation and maintenance.
•
Provide a clear path to the CPM1 for operation and maintenance. High-voltage
equipment or power lines could be dangerous if they are in the way during rou-
tine operations.
•
The PC will be easiest to access if the panel or cabinet is installed about 3 to 5
feet off of the floor.
3-3
Installing the CPM1
3-3-1 CPM1 Orientation
The CPM1 must be installed in the position shown below to ensure adequate
cooling.
Correct
Installing the CPM1
Section 3-3
Summary of Contents for SYSMAC CPM1
Page 1: ...Cat No W262 E1 4 Programmable Controllers SYSMAC CPM1 OPERATION MANUAL ...
Page 2: ...CPM1 Programmable Controllers Operation Manual Revised February 1998 ...
Page 116: ...105 Appendix B Dimensions All dimensions are in millimeters CPM1 10CDR j 121 130 85 81 90 ...
Page 118: ...Appendix B Dimensions 107 CPM1 20EDR 81 90 171 180 85 ...
Page 119: ...Appendix B Dimensions 108 CPM1 CIF01 90 81 21 30 205 50 56 CPM1 CIF11 90 81 21 30 205 50 61 ...