The following example shows how to save the comparison result immedi-
ately. If the content of HR 8 is greater than that of 9, 0200 is turned ON; if the
two contents are equal, 0201 is turned ON; if content of HR 8 is less than
that of HR 9, 0202 is turned ON. In some applications, only one of the three
OUTs would be necessary, making the use of TR 0 unnecessary. With this
type of programming, 0200, 0201, and 0202 are changed only then CMP(20)
is executed.
CMP(20)
HR 8
HR 9
0000
1905
0200
1907
0202
TR
0
1906
0201
Greater Than
Equal
Less Than
Address
Instruction
Operands
Address
Instruction
Operands
0000
LD
0000
0001
OUT
TR
0
0002
CMP(20)
HR
8
HR
9
0003
LD
TR
0
0004
AND
1905
0005
OUT
0200
0006
LD
TR
0
0007
AND
1906
0008
OUT
0201
0009
LD
TR
0
0010
AND
1907
0011
OUT
0202
The following example uses TIM, CMP(20), and the LE flag (1907) to pro-
duce outputs at particular times in the timer’s countdown. The timer is started
by turning ON 0000. When 0000 is OFF, the TIM (10) is reset and the second
two CMP(20)s are not executed (i.e., executed with OFF execution condi-
tions). Output 0200 is output after 100 seconds; output 0201, after 200 sec-
onds; output 0202, after 300 seconds; and output 0204, after 500 seconds.
Example 1:
Saving CMP(20) Results
Example 2:
Obtaining Indications
during Timer Operation
DATA COMPARE – CMP(20)
Section 5-14