4-6-3
Checking the Program
Once a program has been input, it should be checked for syntax to be sure
that no programming rules have been violated. This check should also be
performed if the program has been changed in any way that might create a
syntax error.
To check the program, input the key sequence shown below. If an error is
discovered, the check will stop and a display indicating the error will appear.
Press SRCH to continue the check. If an error is not found, the program will
be checked through the first END(01), with a display indicating when each 64
instructions have been checked (e.g., display #1 below).
CLR can be pressed to cancel the check after it has been started, and a dis-
play like display #2, in the example, will appear. When the check has reached
the first END, a display like display #3 will appear.
A syntax check can be performed on a program only in PROGRAM mode.
Key Sequence
The following table provides the error types, displays, and explanations of all
syntax errors. The address where the error was generated will also be dis-
played.
Many of the following errors are for instructions that have not been intro-
duced yet. Refer to
4-7 Controlling Bit Status or to Section 5 Instruction Set
for details on these.
Message
Meaning and appropriate response
?????
The program has been destroyed. Reinput the program.
NO END INSTR
There is no END(01) in the program. Write END(01) at the final address in the program.
CIRCUIT ERR
The number of logic blocks and logic block instructions does not agree, i.e., either LD or LD NOT
has been used to start a logic block whose execution condition has not been used by another
instruction or a logic block instruction has been used that does not have the required number of
logic blocks (i.e., unused execution conditions). Check your program.
IL-ILC ERR
IL(02) and ILC(03) are not used in pairs. Correct the program so that each IL(02) has a unique
ILC(03). Although this error message will appear if more than one IL(02) is used with the same
ILC(03), the program will be executed as written. Make sure your program is written as desired
before proceeding.
JMP-JME ERR
JMP(04) and JME(05) are not used in pairs. Match each JMP(04) to a JME(05).
COIL DUPL
The same bit is being controlled (i.e., turned ON and/or OFF) by more than one instruction (e.g.,
OUT, OUT NOT, DIFU(13), DIFD(14), KEEP(11), SFT(10)). Although this is allowed for certain
instructions, check instruction requirements to confirm that the program is correct or rewrite the
program so that each bit is controlled by only one instruction.
DIF OVER
More than 48 DIFU and DIFDs are used in the program. Reduce the number of DIFU(13) and
DIFD(14) used to 48 or less.
LOCN ERR
The instruction currently displayed is in the wrong area. Correct the program.
JME UNDEFD
The corresponding JME for a given JMP does not exist. Correct the program.
JMP UNDEFD
The corresponding JMP for a given JME does not exist. Correct the program.
DUPL
The number of the currently displayed instruction has already been programmed. Correct the
program.
SBN-RET ERR
Incorrect usage of the displayed instruction (SBN or RET). Incorrect SBN usage is caused by
more than one SBN having the same subroutine number. Correct the program.
SBN UNDEFD
The subroutine called by SBS does not exist. Correct the program.
Error Messages
Inputting, Modifying, and Checking the Program
Section 4-6
Summary of Contents for SYSMAC C20K
Page 1: ...Cat No W146 E1 5 Programmable Controllers SYSMAC C20K C28K C40K C60K ...
Page 2: ...K type Programmable Controllers OPERATION MANUAL Revised July 1999 ...
Page 3: ...iv ...
Page 5: ...vi ...
Page 19: ...7 SECTION 2 Hardware Considerations 2 1 Introduction 2 2 Indicators 2 3 PC Configuration ...