98
Examples
The high-speed counter normally provides 16 output bits. If more than 16 are
required, the high-speed counter may be programmed more than once. In
the following program example, the high-speed counter is used twice to pro-
vide 32 output bits.
1813 (normally ON)
0002
MOV(21)
“S1”
DM 32
MOV(21)
“S2”
DM 33
MOV(21)
“S32”
DM 35
HDM(61) 47
HR 0
Transfers limit values
S1 to S32 to DM.
Output thru HR 0
A
1813 (normally ON)
0002
MOV(21)
Transfers limit values
S33 to S64 to DM.
Output thru HR 1
B
“S33”
DM 32
MOV(21)
“S34”
DM 33
MOV(21)
“S64”
DM 35
HDM(61) 47
HR 1
Address
Instruction
Operands
0000
LD
1813
0001
MOV(21)
“S1”
DM
32
0002
MOV(21)
“S2”
DM
33
0003
MOV(21)
“S32”
DM
35
0004
LD
0002
0005
HDM(61)
47
HR
0
0006
LD
1813
0007
MOV(21)
“S33”
DM
32
0008
MOV(21)
“S34”
DM
33
0009
MOV(21)
“S64”
DM
35
0010
LD
0002
0011
HDM(61)
47
HR
1
In this program, each bit in the specified words, HR 0 and HR 1 are turned
ON under the following conditions (where S is the present count value of the
high-speed counter stored as the data of CNT 47):
Where S1
≤
S
≤
S2,
HR 000 is ON.
Where S3
≤
S
≤
S4,
HR 001 is ON.
Where S31
≤
S
≤
S32, HR 015 is ON.
Where S33
≤
S
≤
S34, HR 100 is ON.
Where S63
≤
S
≤
S64, HR 115 is ON.
Extending the Counter
Timer and Counter Instructions
Section 5-11