85
In the following example, 0500 would be turned ON 5.0 seconds after 0000
goes ON and then turned OFF 3.0 seconds after 0000 goes OFF. It is neces-
sary to use both 0500 and 0000 to determine the execution condition for TIM
02; 0000 in an normally closed condition is necessary to reset TIM 02 when
0000 goes ON and 0500 is necessary to activate TIM 02 when 0000 goes
OFF, setting 0500 by resetting TIM 01.
0000
0500
0000
TIM 01
TIM 02
0000
0500
5.0 s
3.0 s
Address
Instruction
Operands
0000
LD
0000
0001
TIM
01
#
0050
0002
LD
0500
0003
AND NOT
0000
0004
TIM
02
#
0030
0005
LD
TIM
01
0006
LD
TIM
02
0007
KEEP(11)
0500
TIM 01
#0050
TIM 02
#0030
S
R
KEEP(11)
0500
5.0 s
3.0 s
The length of time that a bit is kept ON or OFF can be controlled by combin-
ing TIM with OUT or OUT NOT. The following diagram demonstrates how
this is possible. In this example, 0204 would remain ON for 1.5 seconds after
0000 goes ON regardless of the time 0000 stays ON. This is achieved by
using 1000, activated by 0000, to turn ON 0204. When TIM 01 comes ON
(i.e., when the SV of TIM 01 has expired), 0204 will be turned OFF through
TIM 01 (i.e., TIM 01 will turn ON for an normally closed condition, creating an
OFF execution condition for OUT 0204). TIM 01 will also turn OFF 1000 the
next cycle, resetting the one-shot.
0000
TIM 01
1000
1000
1000
TIM 01
1000
0204
0000
0204
1.5 s
1.5 s
Address
Instruction
Operands
0000
LD
1000
0001
AND NOT
TIM
01
0002
OR
0000
0003
OUT
1000
0004
LD
1000
0005
TIM
01
#
0015
0006
LD
1000
0007
AND NOT
TIM
01
0008
OUT
0204
TIM 01
#0015
1.5 s
Example 4:
One-shot Bits
Timer and Counter Instructions
Section 5-11