![background image](http://html1.mh-extra.com/html/omron/sysmac-c200h/sysmac-c200h_operation-manual_742423034.webp)
21
turns one ON then OFF, the specified Link Unit will be restarted. Other con-
trol bits are OFF until set by the user.
Word(s)
Bit(s)
Function
236
00 to 07
Node loop status output area for operating level 0 of
SYSMAC NET Link System
08 to 15
Node loop status output area for operating level 1 of
SYSMAC NET Link System
237
00 to 07
Completion code output area for operating level 0 following
execution of SEND(90)/RECV(98) SYSMAC
LINK/SYSMAC NET Link System
08 to 15
Completion code output area for operating level 1 following
execution of SEND(90)/RECV(98) SYSMAC
LINK/SYSMAC NET Link System
238 to 241
00 to 15
Data link status output area for operating level 0 of
SYSMAC LINK or SYSMAC NET Link System
242 to 245
00 to 15
Data link status output area for operating level 1 of
SYSMAC LINK or SYSMAC NET Link System
246
00 to 15
Not used
247 to 250
00 to 07
PC Link Unit Run Flags or data link status for operating
level 1
08 to 15
PC Link Unit Error Flags or data link status for operating
level 1
251
00 to 15
Remote I/O Error Flags
252
00
SEND(90)/RECV(98) Error Flag for operating level 0 of
SYSMAC LINK or SYSMAC NET Link System
01
SEND(90)/RECV(98) Enable Flag for operating level 0 of
SYSMAC LINK or SYSMAC NET Link System
02
Operating Level 0 Data Link Operating Flag
03
SEND(90)/RECV(98) Error Flag for operating level 1 of
SYSMAC LINK or SYSMAC NET Link System
04
SEND(90)/RECV(98) Enable Flag for operating level 1 of
SYSMAC LINK or SYSMAC NET Link System
05
Operating Level 1 Data Link Operating Flag
06
Host Computer to Rack-mounting Host Link Unit Level 1
Error Flag
07
Rack-mounting Host Link Unit Level 1 Restart Bit
08
CPU-mounting Host Link Unit Error Flag
09
CPU-mounting Host Link Unit Restart Bit
10
Not used.
11
Forced Status Hold Bit (CPU11-E only)
12
I/O Status Hold Bit
13
Rack-mounting Host Link Unit Level 0 Restart Bit
14
Not used.
15
Output OFF Bit
SR Area
Section 3-4
Summary of Contents for SYSMAC C200H
Page 1: ...OPERATION MANUAL C200H CPU01 E 03 E 11 E SYSMAC Programmable Controllers Cat No W130 E1 05 ...
Page 2: ...C200H Programmable Controllers CPU01 E 03 E 11 E Operation Manual Revised June 2003 ...
Page 3: ...iv ...
Page 5: ...vi ...
Page 8: ...TABLE OF CONTENTS ix Glossary 345 Index 363 Revision History 369 ...
Page 342: ...336 Programmer Program Date Page Word Contents Notes Word Contents Notes Data Storage ...
Page 374: ...Cat No W130 E1 05 C200H Programmable Controllers CPU01 E 03 E 11 E OPERATION MANUAL ...