SYSMAC NET Link Systems
Completion
code
Name
Meaning
00
Normal end
Data transfer was completed successfully.
01
Parameter error
SEND(90)/RECV(98) instruction operands are not within specified ranges.
02
Transmission impossible
The System was reset during execution of the instruction or the destination
node is not in the System.
03
Busy error
The destination node is busy and cannot receive the transfer.
04
Transmission error
The line server token was not received.
05
Loop error
An error occurred in the transmission loop.
06
No response
Destination node does not exist or response was not received within the
time limit.
07
Response error
Incorrect response format.
SYSMAC LINK/SYSMAC NET Link Data link status is output to SR 238
through SR 241 for the operating level 0 data link, and to SR 242 through SR
245 for the operating level 1 data link in the SYSMAC NET Link or SYSMAC
LINK System.
The meaning of each bit in these areas differs depending on whether the
data link is in a SYSMAC LINK System or SYSMAC NET Link System, as
shown below.
SYSMAC LINK Systems
Level 0
Level 1
Bits
00 to 03
04 to 07
08 to 11
12 to 15
SR 238
SR 242
Node 1
Node 2
Node 3
Node 4
SR 239
SR 243
Node 5
Node 6
Node 7
Node 8
SR 240
SR 244
Node 9
Node 10
Node 11
Node 12
SR 241
SR 245
Node 13
Node 14
Node 15
Node 16
Each of the above sets of four bits operates as shown below.
Leftmost bit
Middle bits
Rightmost bit
ON when data link is active.
ON when there is a data
communications error.
ON when there is a PC
error.
ON when PC is in RUN
mode.
SYSMAC NET Link Systems
Level 0
Level 1
Bit numbers in header/Registration number in the data link table
PC Error Flags
PC Run Flags
00
01
02
03
04
05
06
07
08
09
10
11
12
13
14
15
SR 238
SR 242
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
SR 239
SR 243
9
10
11
12
13
14
15
16
9
10
11
12
13
14
15
16
SR 240
SR 244
17
18
19
20
21
22
23
24
17
18
19
20
21
22
23
24
SR 241
SR 245
25
26
27
28
29
30
31
32
25
26
27
28
29
30
31
32
PC Link Systems
When the PC belongs to a PC Link System, words 247 through 250 are used
to monitor the operating status of all PC Link Units connected to the PC Link
System. This includes a maximum of 32 PC Link Units. If the PC is in a Multi-
level PC Link System, half of the PC Link Units will be in a PC Link Subsys-
Data Link Status
PC Link Unit Error and Run
Flags
SR Area
Section 3-4
Summary of Contents for SYSMAC C200H
Page 1: ...OPERATION MANUAL C200H CPU01 E 03 E 11 E SYSMAC Programmable Controllers Cat No W130 E1 05 ...
Page 2: ...C200H Programmable Controllers CPU01 E 03 E 11 E Operation Manual Revised June 2003 ...
Page 3: ...iv ...
Page 5: ...vi ...
Page 8: ...TABLE OF CONTENTS ix Glossary 345 Index 363 Revision History 369 ...
Page 342: ...336 Programmer Program Date Page Word Contents Notes Word Contents Notes Data Storage ...
Page 374: ...Cat No W130 E1 05 C200H Programmable Controllers CPU01 E 03 E 11 E OPERATION MANUAL ...