210
In this case, the input data word, IR 010, contains #0014, and f(0014) =
#0726 is output to R, IR 011.
X
Y
$1F20
$0F00
$0726
$0402
(0,0)
$0005
$0014
$001A
$05F0
(x,y)
5-22-9
WATCHDOG TIMER REFRESH– WDT(94)
T: Watchdog timer value
# (00 to 63)
Ladder Symbols
Definer Data Areas
@WDT(94) T
WDT(94) T
When the execution condition is OFF, WDT(94) is not executed. When the
execution condition is ON, WDT(94) extends the setting of the watchdog tim-
er (normally set by the system to 130 ms) by 100 ms times T.
Timer extension = 100 ms x T.
Precautions
If the cycle time is longer than the time set for the watchdog timer, 9F will be
output to the FAL area and the CPU will stop.
If the cycle time exceeds 6,500 ms, a FALS 9F will be generated and the sys-
tem will stop.
Timers might not function properly when the cycle time exceeds 100 ms.
When using WDT(94), the same timer should be repeated in the program at
intervals that are less than 100 ms apart. TIMH(15) should be used only in a
scheduled interrupt routine executed at intervals of 10 ms or less.
Flags
There are no flags affected by this instruction.
5-22-10 I/O REFRESH – IORF(97)
St: Starting word
IR (I/O word only)
Ladder Symbol
E: End word
IR (I/O word only)
Operand Data Areas
IORF(97)
St
E
Description
Special Instructions
Section 5-22
Summary of Contents for SYSMAC C200H
Page 1: ...OPERATION MANUAL C200H CPU01 E 03 E 11 E SYSMAC Programmable Controllers Cat No W130 E1 05 ...
Page 2: ...C200H Programmable Controllers CPU01 E 03 E 11 E Operation Manual Revised June 2003 ...
Page 3: ...iv ...
Page 5: ...vi ...
Page 8: ...TABLE OF CONTENTS ix Glossary 345 Index 363 Revision History 369 ...
Page 342: ...336 Programmer Program Date Page Word Contents Notes Word Contents Notes Data Storage ...
Page 374: ...Cat No W130 E1 05 C200H Programmable Controllers CPU01 E 03 E 11 E OPERATION MANUAL ...