223
Special I/O Unit Refresh
Unit
Time required
C200H-ID501/215
0.8 ms each
C200H-OD501/215
0.8 ms each when set for 32 I/O pts.
C200H-MD501/215
1.8 ms each when set for I/O timing
C200H-CT001-V1/CT002
2.2 ms
C200H-NC111/NC112
3.0 ms
C200H-NC211
6 ms
C200H-AD001
2.3 ms
C200H-AD002
2.0 ms
C200H-DA001
2.0 ms
C200H-TS001/TS101
1.8 ms each
C200H-TC
jjj
(see note 1)
4.0 ms each
C200H-ASC02
2.0 ms each normally, 6.0 ms for @ format
C200H-IDS01-V1/IDS21
2.5 ms each normally, 6.5 ms for command transfer
C200H-OV001
4.5 ms
C200H-TV
jjj
(see note 1)
4.0 ms
C200H-PID0
j
(see note 2)
4.0 ms
C200H-FZ001
2.3 ms
C200H-CP114
3.2 ms
Note
1.
jjj
= 001/002/003/101/102/103
2.
j
=1/2/3
Cycle Time
Section 6-1