![background image](http://html.mh-extra.com/html/omron/nt20s/nt20s_operation-manual_744540086.webp)
67
Starting the NT20S
Section 3-2
3-2
Starting the NT20S
When the NT20S is started, it will enter the RUN mode if system settings and
screen data registration have been completed. If no screen data has been regis-
tered or the screen data are destroyed, the System Menu will be displayed.
Before turning ON the power, check the following DIP switch settings on the
NT20S.
S
SW2-3 “Switch to the System Menu enabled/disabled” is set to OFF (enabled).
S
SW2-1 “Screen data forced initialize Yes/No” is set to No (ineffective).
For the DIP switch settings of the unit, refer to the “DIP switch settings” (page 24).
3-2-1
Changing the System Settings etc.
Follow the procedure below to change the system settings or screen data con-
tents.
Procedure
1. Turn ON the power to the NT20S.
The NT20S will enter the RUN mode and the start-up screen will be displayed.
The start-up screen varies according to registered screen data.
2. Press appropriate touch switches to display the System Menu, and change
system settings. For the method for calling the System Menu, refer to the “Op-
erations with the System Menu” (page 70).
Note:
If the NT20S has failed to start up normally; an error message is displayed or no
screen is displayed, memory needs to be initialized.
For the memory initializing procedure, refer to Section 3-4 Initializing memory
(page 72).
Summary of Contents for NT20S
Page 1: ...Cat No V020 E1 04 NT20S Programmable Terminal OPERATION MANUAL ...
Page 2: ...i ...
Page 3: ...ii ...
Page 4: ...iii NT series Programmable Terminal Operation Manual Revised August 1997 ...
Page 5: ...iv ...
Page 7: ...vi ...
Page 11: ...x ...
Page 19: ...xviii ...
Page 129: ...110 ...
Page 169: ...150 ...
Page 253: ...234 ...