Comm. Type
Key Sound
Buzzer Sound
Host Link
OFF
Bk light Off
Tool Mode
OFF
None
NT20M
(1/2)
Quit
WRT&
EXIT
MEMORY SW MENU
Page
95
Various System Settings
Section 3-8
Repeatedly pressing the “BK
light Off” touch switch cycles
through the setting options “10
min”, 1 hour, and None, in that
order.
(The figure to the left shows the
NT20S-ST121-V2 screen.)
To set and quit the menu, press the [WRT&EXIT] touch switch. To quit without set-
ting, press [Quit].
S
None: The backlight off function is not used. As long as no operation is per-
formed, the same screen remains to be displayed.
S
10 minutes: The backlight will be turned off when no operation has been per-
formed for 10 minutes.
S
1 hour: The backlight will be turned off when no operation has been performed
for 1 hour.
Caution:
Do not press touch switches carelessly while the backlight is off or while nothing is
displayed on the screen.
Otherwise the system may operate unpredictably.
Only press touch switches after confirming system safety.
Correct Use:
Continuous display of the same pattern for an extended time (as a guide, about 1
hour) will lead to the formation of an afterimage.
In order to prevent this, either use the screen saver function or periodically switch
screens.
3-8-4
Support Tool Mode Setting (NT20S-ST121-EV3/ST122-V1 Only)
By setting “Tool Mode” to “NT20M”, the NT20M-ST121-EV3/ST122-V1 can be
used in the same way as the conventional NT20M, and it becomes possible to use
the NT20M/NT2000M/NT600M support tool (Ver.4.
j
).
However, the following restrictions apply when “NT20M” is set:
S
Ver.5 of the direct connection function cannot be used.
S
The PT type setting must be “NT20M”.
S
High-speed data transfer with the support tool is not possible.
S
It is not possible to transfer the direct information alone.
S
When screen data transmission is in screen units, simultaneous transmission of
multiple screens is not possible. An attempt to transmit multiple screens may
destroy the screen data.
S
When screen data transmission is in screen units, transmission with verification
set is not possible.
S
The image data memory must be initialized before starting transfer in file units.
S
Screen data for RS-232C communication cannot be used.
Summary of Contents for NT20S
Page 1: ...Cat No V020 E1 04 NT20S Programmable Terminal OPERATION MANUAL ...
Page 2: ...i ...
Page 3: ...ii ...
Page 4: ...iii NT series Programmable Terminal Operation Manual Revised August 1997 ...
Page 5: ...iv ...
Page 7: ...vi ...
Page 11: ...x ...
Page 19: ...xviii ...
Page 129: ...110 ...
Page 169: ...150 ...
Page 253: ...234 ...