4-1 Troubleshooting
4-1-4
Error Message When Using Programming Console Function
97
4-1-4
Error Message When Using Programming Console
Function
Message
Probable cause
Countermeasure
Communication Error by
following cases:
•
Disconnection of the
connecting cable.
•
Programming Console is
connected to the PLC.
•
Communication setting in
the PLC is incorrect.
Communications error occurred
while starting the Programming
Console function or operating the
Programming Console function.
•
Check if the connecting cable is connected.
•
Check the connection port of the PT. If the
Programming Console is connected to the
CPU Unit of CS/CJ Series 232C port or
peripheral port, Programming Console
becomes effective.
•
Programming Console function stopped
because the Programming Console is
connected while operating the Programming
Console function. Press the
OK
Button to
exit the Programming Console function and
return the Ladder Monitor screen. To restart
the Programming Console function, select
Start up Programming Console from the
pop-up menu by pressing the
Mode
Button,
again.
Programming Console
function can only be used
when the Unit No. 0 is set.
Check communications
setting in the System Menu.
A unit number other than 0 is set
for the unit number on the Comm.
Tab of the System Menu of PT.
Set 0 for the Unit No.
The Programming Console function cannot be
used if the number except 0 is set for the Unit
No.
To use the Programming
Console function, the cable
must be connected the
RS-232C port or peripheral
port built in the CPU. Check
the cable connection.
The cable is not connected to
RS-232C port or peripheral port in
the CPU.
Connect the cable to the RS-232C port or
peripheral port.
Cannot find the active port.
Check communications
setting in the System Menu.
Neither port A nor port B is set in
the
Change Host
Dialog Box of
Ladder Monitor.
Ladder Monitor/Programming Console function
can be used when the port A or port B of PT is
set.
Set port A or port B on the
Change Host
Dialog
Box of Ladder Monitor.
When PLC is set to memory
write protection,
Programming Console cannot
be used. Check if pin 1 of PLC
is set to OFF.
Writing is disabled for the PLC.
Turn OFF pin 1 of the DIP switch on the PLC to
enable writing.
Cannot be switched to the
Programming Console
function. Check the Memory
Card
Files that are necessary to start
the Programming Console
function do not exist in the Memory
Card.
Cannot access to the Memory
Card because of Memory Card
error.
Copy all the necessary files from the CD-ROM
to the Memory Card again.
Check whether the Memory Card can be
loaded correctly on a computer.
When is set FINS write
protection of by way of
network, Programming
Console cannot be used.
A 1:N NT Link connection was
made with a host that had FINS
write protection via the network
enabled.
To use Programming Console functions, select
OFF for
Validate FINS write protection via
network
in the PLC Setup at the
CX-Programmer.
Summary of Contents for ns series
Page 2: ......
Page 15: ...NS Series Ladder Monitor OPERATION MANUAL LADDER MONITOR ...
Page 18: ......
Page 19: ...Section 1 Introduction ...
Page 31: ...Section 2 Installation ...
Page 43: ...Section 3 Basic Operation ...
Page 93: ...Section 4 Troubleshooting ...
Page 100: ...4 1 Troubleshooting 4 1 4 Error Message When Using Programming Console Function 98 ...
Page 101: ...Appendices ...
Page 106: ...A 2 Standard Models 104 ...
Page 107: ...NS Series Ladder Monitor OPERATION MANUAL I O Comment Extracting Tool ...
Page 109: ...Section 1 Introduction ...
Page 118: ...1 5 Specifications 12 ...
Page 119: ...1 5 Specifications Section 2 Installation ...
Page 121: ...2 1 Installing the I O Comment Extracting Tool Section 3 Basic Operation ...
Page 128: ...3 3 Uninstalling the I O Comment Extracting Tool 22 ...
Page 129: ...Appendix ...
Page 131: ......