3 Functions of NB-Designer
3-328
NB-series Programmable Terminals NB-Designer Operation Manual(V106)
Others:
The following addresses will be valid after the restart. They are retained even if power failure occurs in
readable or writable addresses.
Note
If the address exceeds 10,000, the address cannot be modified during simulation. But the read operation is
available (For example, the Number Input component with the address of LW10005 will be displayed as 2006
during the test, and it can’t be modified to the other value during the test. But it can be modified only after it
is downloaded to the PT. ).
System parameter settings
Addresses
Descriptions
Comments
10010
No. of Initial Screen
It ranges from 0 to 32767.
10011
Screen saver (Backlight)
0 (Disable Screen saver)
1 to 600 minutes (enabled)
10012
Buzzer
0: Disabled, 1: Enabled
10013
Common Sheet/Pop-up Screen
0: Normal, 1: At the top of all the other screens
10014
Placing Common Sheet
0: At the bottom of Base Screen, 1: At the top of Base Screen
10015
Number of stored events
It ranges from 0 to 65535. If it is set to “0”, the event
data will be cleared after the restart.
10016
Source of RTC
0: PLC (LW), 1: Internal RTC.
10017
Default language
It ranges from 0 to 3.
10018
Reserved by system
Security level
Addresses
Descriptions
Comments
10022~
10023
Password/0
Double-word is occupied.
10024~
10025
Password/1
Double-word is occupied.
10026~
10027
Password/2
Double-word is occupied.
10118~
10143
Password/3 to 15
Double-word is occupied × 13.
Initial Communications Parameters
Addresses
Descriptions
Comments
10030~
10033
IP Address of the NB Units
If it is changed, restart is needed
i.e. IP Address: 192.168.250.1
LW10030:1,
LW10031:250,
LW10032:168,
LW10033:192
10034
Port Number of the NB Unit
If it is changed, restart is needed
10035
Reserved by system
10036
COM 2 operation mode
0: RS-232, 1: RS-422, 2: RS-485.
10037~
10038
COM 2 Baud Rate
Double-word.
10039
COM 2 Data Bit
10040
COM 2 Parity Bit
10041
COM 2 Stop Bit
10042
COM 2 Station No. (PT Station No.)
10043~
10044
COM 2 PLC timeout duration
10045~
10046
COM 2 Protocol Time Out 1
10047~
10048
COM 2 Protocol Time Out 2
Summary of Contents for NB10W-TW01B
Page 4: ......
Page 10: ...Terminology 6 NB series Programmable Terminals NB Designer Operation Manual V106 ...
Page 528: ...8 Web Interface 8 10 NB series Programmable Terminals NB Designer Operation Manual V106 ...
Page 544: ...Appendices A 16 NB series Programmable Terminals NB Designer Operation Manual V106 ...
Page 546: ...Revision 2 NB series Programmable Terminals NB Designer Operation Manual V106 ...
Page 547: ......