![Omron NB10W-TW01B Operation Manual Download Page 198](http://html.mh-extra.com/html/omron/nb10w-tw01b/nb10w-tw01b_operation-manual_743122198.webp)
3 Functions of NB-Designer
3-156
NB-series Programmable Terminals NB-Designer Operation Manual(V106)
4
Switch to the [Save Data History] tab and determine whether to check “Save to Recipe Data
Field”.
Save to Recipe Data Field:
After this option is checked and the Start Address. is set, the
sampling data can be saved to the Recipe Data Field(RW).
Data History for the Data Log is saved in the [Start Address] as the top, and the memory area
includes the Information Area with the size of 40 bytes (i.e. 20 words), and the Time Area with
the size of Sampling Pages × Sampling Points/Page × 4 words (If “Save Time” is checked.) and
the Data Area with the size of Sampling Pages × Sampling Points/Page × Word Length.
When the multiple historical Data Logs saved into the recipe are used, the user must ensure
that the memory area of each trend curves will not overlap each other, otherwise, the data
mistakes will occur.
5
Press the [OK] button to adjust the position and size of the Data Log component.