213
Using FINS Applications
Section 8-5
Example: Network Settings (Driver Tab Page)
■
System Configuration Example 2: Using Routing Tables
In this example, an online connection is made via the Ethernet to a PLC on a
Controller Link network (PLC 3 below) from a CX-Programmer/CX-Integrator
connected to the Ethernet network.
Conditions
• FINS/UDP method
• IP address conversion: Automatic generation method (dynamic)
CX-Programmer's Change PLC Dialog Box
Settings for target PLC (PLC3)'s Change PLC Dialog Box
Setting
PLC name
PLC3
Network classification
Ethernet
Network Tab
Page
FINS destination
FINS transmission
source address
1
Network number
2
Node address
3
Frame length
2,000 bytes
Response monitor time
2 seconds
CX-Programmer/CX-Integrator
Ethernet port
Node address: 1
IP address: 192.168.250.1
Ethernet or EtherNet/IP
(network address 1)
Routing
according to
routing table
Controller
Link Unit
EtherNet/IP Unit
IP address conversion: Automatic generation method (dynamic)
Gateway between networks
PLC1
Controller Link Unit
Target PLC
Controller Link Unit
Node address 2
Node address 3
Controller Link (network address 2)
PLC2
PLC3
EtherNet/IP Unit node address: 2
EtherNet/IP Unit IP address: 192.168.250.2
EtherNet/IP Unit unit number: 0
Controller Link Unit node address: 1
Controller Link Unit unit number: 1
Routing to final network address 2
requires relaying through node
address 2 of relay network address
1 (EtherNet/IP Unit).
Summary of Contents for CJ2H-CPU6 - REV 02-2010
Page 2: ......
Page 4: ...iv...
Page 6: ...vi...
Page 14: ...xiv...
Page 18: ...xviii...
Page 38: ...12 Network Configurator Overview Section 1 5...
Page 58: ...32 Selecting the Network Devices Section 2 3...
Page 116: ...90 Auxiliary Area Data Section 4 5...
Page 222: ...196 Message Communications Errors Section 7 6...
Page 364: ...338 Using the Backup Tool Section 13 3...
Page 402: ...376 CS CJ series Ethernet Unit Function Comparison Appendix A...
Page 404: ...378 Ethernet Network Parameters Appendix B...
Page 406: ...380 TCP Status Transitions Appendix C...
Page 452: ...426 Precautions for Using Windows XP Vista or Windows 7 Appendix G...
Page 460: ...434 Index...
Page 462: ...436 Revision History...
Page 463: ......