289
I/O Response Time in Tag Data Links
Section 10-3
(6) Output ON response time
This is the delay time for the external output device from when the output bit
turns ON in the memory of the CPU Unit until the output is actually performed.
In this system configuration, the delay time for an output relay is 2.0 ms. Also,
one CPU cycle time is required until the data is stored in the memory area of
the CPU Unit.
The maximum tag data link I/O response time for this system configuration
found from the total of (1) to (6) is 124 ms.
Note
The I/O response time may be longer due to noise, or other events.
D
Number of data trans-
missions
A
10 m sec >
C
6.15 m sec
To meet the condition to enable processing
in one data transmission, the number of
transmissions is the same as
B
plus 1.
(Delay of one CPU Unit cycle time)
4
Total:
(5) Receive data process-
ing time
A
Cycle time
×
D
Number of data trans-
missions
60 msec
Item Time
A
CPU Unit cycle time of PLC #2
15 msec
B
Output relay delay time
2.0 msec
Total:
(6) Node 2 (PLC #2) output ON response time
17.0 msec
(1) Node 1 (PLC #1) input ON response time
11.5 msec
(2) Node 1 (PLC #1) send data processing time
20 msec
(3) Packet Interval (RPI)
10 msec
(4) Network Transmission Delay Time
5.5 msec
(5) Node 2 (PLC #2) receive data processing time
60 msec
(6) Output ON response time
17 msec
Maximum I/O response performance (total of (1) to (6))
124 msec
Item Calculation
formula
Time
Summary of Contents for CJ2H-CPU6 - REV 02-2010
Page 2: ......
Page 4: ...iv...
Page 6: ...vi...
Page 14: ...xiv...
Page 18: ...xviii...
Page 38: ...12 Network Configurator Overview Section 1 5...
Page 58: ...32 Selecting the Network Devices Section 2 3...
Page 116: ...90 Auxiliary Area Data Section 4 5...
Page 222: ...196 Message Communications Errors Section 7 6...
Page 364: ...338 Using the Backup Tool Section 13 3...
Page 402: ...376 CS CJ series Ethernet Unit Function Comparison Appendix A...
Page 404: ...378 Ethernet Network Parameters Appendix B...
Page 406: ...380 TCP Status Transitions Appendix C...
Page 452: ...426 Precautions for Using Windows XP Vista or Windows 7 Appendix G...
Page 460: ...434 Index...
Page 462: ...436 Revision History...
Page 463: ......