242
Sending Explicit Messages
Section 9-1
Class ID (command):
The class ID of the destination of the explicit message.
Instance ID (command):
The instance ID of the destination of the explicit message.
Service data (command, response):
The data defined for the services codes.
No. of bytes received (response):
The number of bytes received from the destination node address (remote
node).
Destination node address (remote node):
The node address of the OMRON Special I/O Slave Unit or Slave manufac-
tured by another company to which the explicit message was sent is returned.
Error code (response):
An error code defined in EtherNet/IP (1-byte general status and 2-byte addi-
tional status) is returned. The data format is DeviceNet-compatible (2 bytes
total), so the returned Error Code is converted to the 1-byte general status
and a 1-byte additional status (high byte only).
Description
• The EXPLICIT MESSAGE SEND command is used to send an EtherNet/
IP-defined explicit message to another company’s node and receive a
response.
• Unlike other FINS commands, the destination of a EXPLICIT MESSAGE
SEND command’s control data is the local node’s EtherNet/IP Unit or
built-in EtherNet/IP port, and the actual destination node is specified in
the command’s route path.
Always specify the local node’s EtherNet/IP Unit or built-in EtherNet/IP port
in the CMND(490) instruction’s control data. An error will occur if another
node’s Master Unit is specified as the destination.
• When an EtherNet/IP Unit or built-in EtherNet/IP port receives an explicit
message, it automatically returns a response to the message.
• A time of 2 s is used for request service processing timeouts.
Set the CMND(490) instruction’s timeout set value to 2 s or longer.
When there is a timeout, the error code will be 0102 hex.
When the CMND(490) instruction’s timeout set value is less than 2 s, a
FINS timeout error response of 0205 hex may occur.
Note
1.
For details on the parameters of explicit messages, refer to the EtherNet/
IP specifications.
2.
The Open DeviceNet Vendor Association, Inc. (ODVA) can be contacted at
the following address to obtain copies of the EtherNet/IP and CIP specifi-
cations.
ODVA Headquarters
4220 Varsity Drive, Suite A
Ann Arbor, Michigan 48108-5006
USA
TEL: 1 734-975-8840
FAX: 1 734-922-0027
Email [email protected]
WEB www.odva.org
Summary of Contents for CJ2H-CPU6 - REV 02-2010
Page 2: ......
Page 4: ...iv...
Page 6: ...vi...
Page 14: ...xiv...
Page 18: ...xviii...
Page 38: ...12 Network Configurator Overview Section 1 5...
Page 58: ...32 Selecting the Network Devices Section 2 3...
Page 116: ...90 Auxiliary Area Data Section 4 5...
Page 222: ...196 Message Communications Errors Section 7 6...
Page 364: ...338 Using the Backup Tool Section 13 3...
Page 402: ...376 CS CJ series Ethernet Unit Function Comparison Appendix A...
Page 404: ...378 Ethernet Network Parameters Appendix B...
Page 406: ...380 TCP Status Transitions Appendix C...
Page 452: ...426 Precautions for Using Windows XP Vista or Windows 7 Appendix G...
Page 460: ...434 Index...
Page 462: ...436 Revision History...
Page 463: ......