214
Using FINS Applications
Section 8-5
CX-Programmer's FINS/UDP Tab Page in Edit Parameters Dialog Box
Same as for System Configuration Example 1.
Routing Table Settings and Transfer to Each PLC
Set the routing tables with CX-Integrator, and transfer them.
1.
Using CX-Integrator, connect online, and select Routing table
−
Settings.
Then create FINS local routing tables (a local network table and a relay
network table).
Example: PLC 1 Routing Table Settings
• Local Network Table
• Relay Network Table
None
Example: PLC 2 and PLC 3 Routing Table Settings
• Local Network Table
• Relay Network Table
In order to relay from PLC2/3 to the final network number 1, it is necessary
to relay via node address 1 (i.e., the Controller Link Unit) on relay network
number 2.
2.
Save the routing table file (File - Save local routing table file).
3.
Next, to connect online, select Communication Settings from the Net-
work Menu. For each PLC, register a PLC with a direct serial connection
(node address: 0), and select it.
4.
With the CX-Integrator, select Work Online from the Network Menu.
5.
Select Tools - Start Routing table, read the saved file, and select Op-
tions - Transfer to PLC. Click Yes to transfer the routing tables to the con-
nected PLC.
Driver Tab Page
Workstation node address
1
Automatic generation method
Not selected
IP address
192.168.250.2 (Eth-
erNet/IP Unit or
built-in EtherNet/IP
port IP address)
Port number
9600
Unit number
Local network number
0
1
1
2
Unit number
Local network number
0
2
Final network number
Relay network number
Relay node address
1
2
1
Settings for target PLC (PLC3)'s Change PLC Dialog Box
Setting
Summary of Contents for CJ2H-CPU6 - REV 02-2010
Page 2: ......
Page 4: ...iv...
Page 6: ...vi...
Page 14: ...xiv...
Page 18: ...xviii...
Page 38: ...12 Network Configurator Overview Section 1 5...
Page 58: ...32 Selecting the Network Devices Section 2 3...
Page 116: ...90 Auxiliary Area Data Section 4 5...
Page 222: ...196 Message Communications Errors Section 7 6...
Page 364: ...338 Using the Backup Tool Section 13 3...
Page 402: ...376 CS CJ series Ethernet Unit Function Comparison Appendix A...
Page 404: ...378 Ethernet Network Parameters Appendix B...
Page 406: ...380 TCP Status Transitions Appendix C...
Page 452: ...426 Precautions for Using Windows XP Vista or Windows 7 Appendix G...
Page 460: ...434 Index...
Page 462: ...436 Revision History...
Page 463: ......