147
Setting Tag Data Links
Section 6-2
4.
If the tag set’s size is changed in either the originator or target after the
connection was set, the size will not match the other node and a parameter
data mismatch will occur. In this case, if the connection settings have been
changed, be sure to check the connections. (Refer to 6-2-17 Checking
Connections.)
Automatically Setting
Connections
Tag set names set for devices can be automatically detected to automatically
set connections between input and output tag sets with the same name (or
the same names excluding specified ellipses). Connections are automatically
set under the following conditions.
Example 1: Automatic Connections with the Same Tag Set Names
The following connections would automatically be set if there is an output tag
set named A_Signal at node A and input tag sets named A_Signal at nodes B
and C.
Output tag set names
Except for specified ellipses, the output tag set name
must be the same as the input tag set name.
Ellipses can be set for the beginning or end of tag set
names.
Input tag set names
Except for specified ellipses, the input tag set name
must be the same as the output tag set name.
Ellipses can be set for the beginning or end of tag set
names.
Connection types
The connection type must be Input Only.
Multicast and single cast connection types can be
specified when executing a connection.
RPI
The default setting is used.
Timeouts
The default setting is used.
Connection
EtherNet/IP
Output tag set: A_Signal
Node A
Input tag set: A_Signal
Node B
Input tag set: A_Signal
Node C
Connection
Excluded characters: None
Summary of Contents for CJ2H-CPU6 - REV 02-2010
Page 2: ......
Page 4: ...iv...
Page 6: ...vi...
Page 14: ...xiv...
Page 18: ...xviii...
Page 38: ...12 Network Configurator Overview Section 1 5...
Page 58: ...32 Selecting the Network Devices Section 2 3...
Page 116: ...90 Auxiliary Area Data Section 4 5...
Page 222: ...196 Message Communications Errors Section 7 6...
Page 364: ...338 Using the Backup Tool Section 13 3...
Page 402: ...376 CS CJ series Ethernet Unit Function Comparison Appendix A...
Page 404: ...378 Ethernet Network Parameters Appendix B...
Page 406: ...380 TCP Status Transitions Appendix C...
Page 452: ...426 Precautions for Using Windows XP Vista or Windows 7 Appendix G...
Page 460: ...434 Index...
Page 462: ...436 Revision History...
Page 463: ......