362
Connection Status Codes and Error Processing
Section 14-3
01
0316
Error code returned from target:
There was a parameter error in
the frame used to close the con-
nection.
This error does
not occur.
Depends on the tar-
get’s specifications.
(Contact the target
device’s manufac-
turer.)
Depends on the orig-
inator’s specifica-
tions. (Contact the
originator device’s
manufacturer.)
01
031C
Error code generated in origina-
tor:
Some other error occurred.
This error does
not occur.
The originator gener-
ates this code when
an unsupported
response code is
returned from the
target in reply to a
connection-opening
request.
Depends on the orig-
inator’s specifica-
tions. (Contact the
originator device’s
manufacturer.)
08
---
Error code returned from target:
There is no Forward Open or
Large Forward Open service in
the target device.
This error does
not occur.
Depends on the tar-
get’s specifications.
(Contact the target
device’s manufac-
turer.)
Depends on the orig-
inator’s specifica-
tions. (Contact the
originator device’s
manufacturer.)
D0
0001
Error code generated in origina-
tor:
The connection operation is
stopped.
The connection
was stopped
because the Tag
Data Link Stop Bit
was turned ON, or
the settings data
is being down-
loaded.
Either turn ON the
Tag Data Link
Start Bit, or wait
until the settings
data has been
downloaded.
Includes Control-
ler stop errors,
Unit failure, and
EM bank files at
the refresh desti-
nation. To handle
these errors, refer
to 14-2-1Errors
Occurring at the
EtherNet/IP Unit
or built-in Ether-
Net/IP port.
The meaning of this
error code is defined
by each vendor, so it
depends on the tar-
get’s specifications.
(Contact the target
device’s manufac-
turer.)
Depends on the orig-
inator’s specifica-
tions. (Contact the
originator device’s
manufacturer.)
D0
0002
Error code generated in origina-
tor:
The connection is being opened
(opening processing in
progress).
Wait until the
opening process-
ing is completed.
The meaning of this
error code is defined
by each vendor, so it
depends on the tar-
get’s specifications.
(Contact the target
device’s manufac-
turer.)
Depends on the orig-
inator’s specifica-
tions. (Contact the
originator device’s
manufacturer.)
Connection status
Source of error
Handling
General
Status
(hex)
Additional
Status
(hex)
Configuration 1
Configuration 2
Configuration 3
Summary of Contents for CJ2H-CPU6 - REV 02-2010
Page 2: ......
Page 4: ...iv...
Page 6: ...vi...
Page 14: ...xiv...
Page 18: ...xviii...
Page 38: ...12 Network Configurator Overview Section 1 5...
Page 58: ...32 Selecting the Network Devices Section 2 3...
Page 116: ...90 Auxiliary Area Data Section 4 5...
Page 222: ...196 Message Communications Errors Section 7 6...
Page 364: ...338 Using the Backup Tool Section 13 3...
Page 402: ...376 CS CJ series Ethernet Unit Function Comparison Appendix A...
Page 404: ...378 Ethernet Network Parameters Appendix B...
Page 406: ...380 TCP Status Transitions Appendix C...
Page 452: ...426 Precautions for Using Windows XP Vista or Windows 7 Appendix G...
Page 460: ...434 Index...
Page 462: ...436 Revision History...
Page 463: ......