Mounting to a PLC
Section 3-3
3-3
Mounting to a PLC
3-3-1
Mounting to a CS-series PLC
EtherNet/IP Units can be mounted to any slot in a CS-series CPU Rack or a
CS-series Expansion CPU Rack, but the number of slots to which they can be
mounted depends on the Backplane. Up to four EtherNet/IP Units can be
mounted to a single PLC. If it is mounted in combination with other CPU Bus
Units (e.g., Controller Link Units), the maximum total number of CPU Bus
Units that can be mounted is 8.
Note
Tighten PLC Backplane mounting screws to a torque of 0.9 N
⋅
m, and the
Unit’s screws to a torque of 0.4 N
⋅
m.
Note
The CS1W-EIP21 EtherNet/IP Unit’s maximum current consumption is
410 mA. Be sure that the total current consumption of all the Units connected
to the same CPU Backplane or Expansion Backplane does not exceed the
output capacity of the Power Supply Unit.
3-3-2
Mounting to a CJ-series PLC
EtherNet/IP Units can be mounted in a CJ-series CPU Rack or a CJ-series
Expansion CPU Rack. Connect the EtherNet/IP Unit in any of the positions
shown below using the sliders on the top and bottom of the Unit. Up to seven
EtherNet/IP Units can be mounted for a CJ2H-CPU
@@
-EIP CPU Unit
(enabling up to eight EtherNet/IP ports if you include the built-in EtherNet/IP
port). Up to two EtherNet/IP Units can be mounted for a CJ2M-CPU3
@
CPU
Unit.
If EtherNet/IP Units are mounted in combination with other CPU Bus Units
(e.g., Controller Link Units), the maximum total number of CPU Bus Units that
can be mounted is 16.
CS1W-BI033/BI053/BI083/BI103 CS-series Expansion Backplane
3, 5, 8, or 10 slots
CS1W-BC023/BC033/BC053/BC083/BC103 CPU Backplane
CS-series CPU Rack with
2, 3, 5, 8, or 10 slots
Can be mounted in any slot.
CS1W-BI033/BI053/BI083/BI103 CS-series Expansion Backplane
CS-series Expansion Rack with
3, 5, 8, or 10 slots.
Up to eight Units can be mounted
to the slots shown in the diagrams
on the left.
3, 5, 8, or 10 slots
2, 3, 5, 8, or 10 slots
(Expansion Backplane not possible with 2-slot CPU Backplane.)
CPU: CPU Unit
PS: Power Supply Unit
CPU
PS
PS
PS
Can be mounted in any slot.
CS-series Expansion Rack with
3, 5, 8, or 10 slots.
Can be mounted in any slot.
Summary of Contents for CJ2H-CPU6 - REV 02-2010
Page 2: ......
Page 4: ...iv...
Page 6: ...vi...
Page 14: ...xiv...
Page 18: ...xviii...
Page 38: ...12 Network Configurator Overview Section 1 5...
Page 58: ...32 Selecting the Network Devices Section 2 3...
Page 116: ...90 Auxiliary Area Data Section 4 5...
Page 222: ...196 Message Communications Errors Section 7 6...
Page 364: ...338 Using the Backup Tool Section 13 3...
Page 402: ...376 CS CJ series Ethernet Unit Function Comparison Appendix A...
Page 404: ...378 Ethernet Network Parameters Appendix B...
Page 406: ...380 TCP Status Transitions Appendix C...
Page 452: ...426 Precautions for Using Windows XP Vista or Windows 7 Appendix G...
Page 460: ...434 Index...
Page 462: ...436 Revision History...
Page 463: ......