Adjusting the Communications Load
Section 10-2
Method 2: Changing a Particular Device’s RPI Setting
The usage of capacity can be adjusted for only a particular device by
changing the packet intervals (RPI) for all of the device’s connections to-
gether. In this case, the usage of capacity will also change for the devices
that are the target devices of the connection which was adjusted.
a.
Click the Set Packet Interval (RPI) Button at the bottom of the Usage
of Device Bandwidth Dialog Box.
b.
The Set Packet Interval (RPI) Dialog Box will be displayed. In the Tar-
get Device Area, deselect the target devices that are not being adjust-
ed by removing the check marks.
c.
Input a new RPI value, and click the OK Button.
Method 3: Changing a Particular Connection’s RPI Setting
The usage of capacity can be adjusted by individually changing the packet
intervals (RPI) setting for a particular connection. In this case, the usage
of capacity will also change for the device that is the target device of the
connection which was adjusted.
Summary of Contents for CJ2H-CPU6 - REV 02-2010
Page 2: ......
Page 4: ...iv...
Page 6: ...vi...
Page 14: ...xiv...
Page 18: ...xviii...
Page 38: ...12 Network Configurator Overview Section 1 5...
Page 58: ...32 Selecting the Network Devices Section 2 3...
Page 116: ...90 Auxiliary Area Data Section 4 5...
Page 222: ...196 Message Communications Errors Section 7 6...
Page 364: ...338 Using the Backup Tool Section 13 3...
Page 402: ...376 CS CJ series Ethernet Unit Function Comparison Appendix A...
Page 404: ...378 Ethernet Network Parameters Appendix B...
Page 406: ...380 TCP Status Transitions Appendix C...
Page 452: ...426 Precautions for Using Windows XP Vista or Windows 7 Appendix G...
Page 460: ...434 Index...
Page 462: ...436 Revision History...
Page 463: ......