I/O Data mapping
Section 4-2
58
Index
Sub-index
Object
Default value
1801h
-
Transmit PDO2 parameter
-
1801h
00h
Number of entries
2
1801h
01h
COB-ID
282h
1801h
02h
Transmission Type
254
1802h
-
Transmit PDO3 parameter
-
1802h
00h
Number of entries
2
1802h
01h
COB-ID
382h
1802h
02h
Transmission Type
254
1803h
-
Transmit PDO4 parameter
-
1803h
00h
Number of entries
2
1803h
01h
COB-ID
482h
1803h
02h
Transmission Type
254
1A00h
-
Transmit PDO1 mapping
-
1A00h
00h
Number of entries
4
1A00h
01h
mapped object
20000108h
1A00h
02h
mapped object
20000208h
1A00h
03h
mapped object
20000308h
1A00h
04h
mapped object
20000408h
1A01h
-
Transmit PDO2 mapping
-
1A01h
00h
Number of entries
1
1A01h
01h
mapped object
20020110h
1A02h
-
Transmit PDO3 mapping
-
1A02h
00h
Number of entries
1
1A02h
01h
mapped object
20010108h
1A03h
-
Transmit PDO4 mapping
-
1A03h
00h
Number of entries
1
1A03h
01h
mapped object
20030120h
4-2-4-2 PLC configuration
By default, the C200HW-CORT21-V1 only transfers the four input and output
bytes mapped to the PDOs of the predefined connection set via the control
and status area. This is not enough for the network configuration of this
example. The following additional data objects need to be transferred:
1 x 16-bit OUT
Data transmitted by node 4
1 x 16-bit IN
Data received by node 4
1 x 8-bit IN
Data received by node 5
1 x 64-bit OUT
Data transmitted by node 6
1 x 32-bit IN
Data received by node 7
Summary of Contents for C200HW-CORT21-V1
Page 2: ...C200HW CORT21 V1 CANopen Slave Unit OPERATION MANUAL OMRON Cat No W904 E2 2 ...
Page 3: ......
Page 4: ......
Page 5: ......
Page 6: ...C200HW CORT21 V1 CANopen Slave Unit Operation Manual Produced June 2001 ...
Page 7: ...iv ...
Page 9: ...vi ...
Page 13: ...x ...
Page 47: ...Performance Section 2 3 30 ...
Page 85: ...Control and Status area Section 4 3 68 ...
Page 113: ...Flow diagrams Section 6 6 96 ...
Page 123: ...Maintenance Section 7 3 106 ...
Page 133: ...116 ...
Page 135: ...118 ...
Page 139: ...122 ...
Page 141: ......