![background image](http://html1.mh-extra.com/html/omron/c200h-cp114/c200h-cp114_operation-manual_742477024.webp)
10
Wiring
Section 2-3
Connection Method
Example using G7TC-OC16.
Be sure to lock the connectors securely.
Note If a 24-VDC power supply is not provided, the Data Setting Console and exter-
nal cam output will not function.
Countermeasures to
Noise
In order to prevent malfunctions due to noise, conduct the following counter-
measures.
Use shielded wire for external cam output lines and resolver cable.
Be sure to wire power lines (e.g., AC power supply, electrical power lines) and
control lines (e.g., external cam output lines, resolver cables) in separate
ducts.
Be sure to mount a surge-absorbing diode or surge absorber to an inductive
load (such as a relay, solenoid, or electromagnetic valve). Use a surge-
absorbing diode with a voltage resistance of at least five times the circuit volt-
age.
G79-
@@@
C
Connection Cable
24 VDC 2 A
Cam Positioner Unit
G7TC-OC16
Output Block
RY
RY
DC
SOL
AC
DC Relay
AC Relay
Surge-absorbing
diode
Surge absorber
(Example: Okaya
Electric's CR-50500)
Solenoid, etc.
Surge absorber
(Example: Okaya
Electric's CR-50500)
Summary of Contents for C200H-CP114
Page 1: ...23 5 7 21 0 18 Cat No W224 E1 2 SYSMAC C200H CP114 Cam Positioner Unit...
Page 2: ......
Page 3: ...C200H CP114 Cam Positioner Unit Operation Manual Revised January 2001...
Page 4: ...iv...
Page 6: ...vi...
Page 8: ......
Page 10: ......
Page 70: ......