7
Switch Settings
Section 2-2
2-2
Switch Settings
Unit Number
The Unit is factory-set to 0.
Note If the Unit number is set to an existing Unit number, an alarm occurs and the
C200H
does not operate. Turn the C200H
power OFF before setting the
Unit number. If the setting is changed with the power ON, the new setting is
not valid until the power is turned OFF and back ON again.
Operation Mode Selector
Note The mode cannot be switched if the Unit has an error.
Unit no.
setting
Allocated
words
Allocated DM
0
100 to 109
DM1000 to DM1010
1
110 to 119
DM1100 to DM1110
2
120 to 129
DM1200 to DM1210
3
130 to 139
DM1300 to DM1310
4
140 to 149
DM1400 to DM1410
5
150 to 159
DM1500 to DM1510
6
160 to 169
DM1600 to DM1610
7
170 to 179
DM1700 to DM1710
8
180 to 189
DM1800 to DM1810
9
190 to 199
DM1900 to DM1910
0
Use a small flat-blade screwdriver to
select the unit number, while being
careful not to set the selector between
two adjacent unit numbers.
RUN
PRG
Setting
Operation
mode
Function
Function item
RUN
RUN mode
Select RUN to place the Cam Positioner Unit
in RUN mode. The following settings are nec-
essary to operate the Cam Positioner Unit
(i.e., to turn cam outputs ON and OFF).
(1) Set banks 1 to 8 at word n + 1.
(2) Turn ON bit 00 of word n (operation flag).
(n = 100 + 10 x Unit no.)
Cam output
Monitoring of the number of process execu-
tion cycles
Monitoring of the present cam angle
Adjustment operation
Bank selection
Origin adjustment
PRG
Program-
ming mode
Select PRG for setting values with the Data
Setting Console.
Cam data setting
Cam data protect setting
Setting the number of revolutions required for
a single process
Origin adjustment