12
Wiring
Section 2-3
2-3-3
Data Setting Console Cables
Connecting Cable
Use the connecting cables in the table below (sold separately) to connect the
unit to the Data Setting Console.
Connection Precautions
Tighten the lock screws after inserting the connector into the unit.
Push the connector firmly into the Data Setting Console until the clips fully
lock.
Power is supplied from the Cam Positioner Unit via connection cable. If power
is not supplied between external cam output terminals (A10, B10) and (A9,
B9), the Data Setting Console cannot be operated.
Install the supplied connector cover when the cable is not connected.
Model
Cable length (L)
C200H-CN225
2 m
C200H-CN425
4 m
L
17.5
10
16.1
17.3
39