50
Specifications
Appendix A
Output Specifications
Note The ON and OFF response times are numbers that depend on the hardware and are not times that can
be controlled by software.
Item
Specifications
Switching capacity
24 VDC 100 mA
Leakage current
160
µ
A max.
Residual voltage
1.8 V max.
ON response time
20
µ
s max. (see note)
OFF response time
20
µ
s max. (see note)
Number of circuits
16 pts./common, 1 circuit
Simultaneous ON points
8 points
External power supply
24 VDC at 2 A max. (including load)